Skip to main content
Schneider Electric LC2K1601FC72 — Contactors

Schneider Electric LC2K1601FC72 TeSys K Reversing Contactor,

MPNLC2K1601FC72
Active

Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤ 440 V 16 A, 1 NC, 127 V AC coil, preassembled with reversing power busbar.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LC2K1601FC72 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LC2K1601FC72 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4
LC2K1601FC72 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K1601FC72 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K1601FC72 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

It's rated AC-3 ≤ 440 V at 16 A and carries a 127 V AC coil, with one NC auxiliary contact built in. The AC-3 and AC-4 utilisation categories mean it's sized for motor switching (starting, stopping, plugging, inching) on squirrel-cage induction motors, not just resistive loads.

Maximum operating altitude is 2000 m without derating. The contactor is rated for shock and vibration per IEC 60068-2-27 and IEC 60068-2-6: it withstands 10 Gn on Y and Z axes (contactor closed) and 4 Gn vibration closed across 5–300 Hz. That makes it usable on mobile equipment or in panels near rotating machinery.

The contactor measures 57 mm deep, 90 mm wide, and 58 mm high. The depth of 57 mm keeps it within the clearance of typical 80 mm deep enclosures.

Frequently asked questions

What are the key ratings for this reversing contactor?

AC-3 ≤ 440 V at 16 A, 690 V rated operational voltage on the power circuit, 127 V AC coil, 1 NC auxiliary contact, 3 poles. IP20 protection, operating temperature -25 to 50 °C.

What compliance standards does the LC2K1601FC72 meet?

Flame retardance V1 per UL 94, plus NF F 16-101 and NF F 16-102 for rail applications. IP20 per VDE 0106. Shock and vibration per IEC 60068-2-27 and IEC 60068-2-6.

MPN
LC2K1601FC72