It is configured as 3 x 3P (three power poles, each normally open) and rated for 6 A in AC-3 utilisation category, meaning it is sized for switching three-phase induction motors under full-load conditions. The coil is wound for 220 V AC control voltage.
The starter is rated for operation up to 2000 m altitude without derating. It carries protective treatment conforming to IEC 60068 and DIN 50016 for damp heat and corrosive atmospheres. Vibration resistance is 2 Gn (contactor open) and 4 Gn (closed) over 5–300 Hz; shock resistance reaches 15 Gn on closed contacts along Y and Z axes. These figures matter if the panel is mounted on mobile equipment or near rotating machinery.