Schneider Electric LP2K1210SD — Contactors

Schneider TeSys K LP2K1210SD reversing contactor, 12 A AC-3,

MPNLP2K1210SD
Obsolete

Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 12 A, 1 NO, 72 V DC coil, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LP2K1210SD — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationResistive load Motor control
LP2K1210SD — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-4 AC-1 AC-3
LP2K1210SD — Contacts & Poles
ParameterValue
Pole configuration3P
LP2K1210SD — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor opened, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on X axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LP2K1210SD — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

It carries three normally-open power poles and one normally-open auxiliary contact, with a 72 V DC coil. The AC-1 rating covers resistive loads at the same current level. IP20 finger protection (per VDE 0106) means it's safe for panel-mount use where operators may reach inside the enclosure. The V1 flame-retardance rating (UL 94) and NF F 16-101 compliance suit rail and transit environments.

Altitude derating starts above 2000 m. The contactor withstands 15 Gn shock (closed) and 4 Gn vibration on Z-axis per IEC 60068-2-6 and -2-27, making it suitable for mobile or rail-mounted gear.

Frequently asked questions

What replaces the LP2K1210SD?

Schneider does not list a direct official successor for this order code. A current-production TeSys K reversing contactor with the same coil voltage and pole count is the closest functional match, but verify auxiliary contact configuration and busbar fit before substituting.

What are the key ratings of the LP2K1210SD?

It is a 3-pole reversing contactor rated 12 A at ≤440 V in AC-3 (motor) duty, with a 72 V DC coil. It includes one normally-open auxiliary contact and carries IP20 protection.

MPN
LP2K1210SD