Schneider Electric MGN25124 — Miniature Circuit Breakers (MCB)

MGN25124 C60H MCB, 1 A D Curve, 3P, 30 kA

MPNMGN25124
Obsolete

Schneider Electric Multi9 C60H series, MGN25124 miniature circuit-breaker, 3-pole, 1 A rated current, D curve, 30 kA breaking capacity at 240 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN25124 — Identification
ParameterValue
Product nameC60
Product rangeMulti9
Product range (series)C60
Product/component typeMiniature circuit-breaker
Device applicationDistribution
MGN25124 — Ratings
ParameterValue
Rated current (In)1 A at 50 °C conforming to EN/IEC 60947-2
Poles configuration3P
Number of protected poles3
Breaking capacity30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity (Ics)15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Rated operational voltage (Ue)440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
MGN25124 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)10000 cycles conforming to EN/IEC 60947-2
Mechanical durability (cycles)20000 cycles
MGN25124 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Control typeToggle
Terminal connection typeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Terminal tightening torquePower circuit: 2 N.m
Wire stripping lengthPower circuit: 14 mm
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width54 mm
Height81 mm
Depth73 mm
Number of 9 mm pitches6
MGN25124 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
Pollution degree3 conforming to EN/IEC 60947-2
MGN25124 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The Schneider Electric MGN25124 is a C60H miniature circuit-breaker from the Multi9 range, rated 1 A with a D curve and 3 poles. It's built to EN/IEC 60947-2, which covers the performance and testing requirements for low-voltage circuit-breakers used in distribution.

The MGN25124 delivers 30 kA Icu at 240 V AC phase-to-phase, 15 kA at 415 V, and 10 kA at 440 V. The Ics (service breaking capacity) is 50% of Icu at each voltage level, so after clearing a fault at 15 kA on a 240 V circuit, the breaker is still rated to carry and switch its rated current. That matters for installations where a fault is cleared and the circuit needs to be re-energized without immediately replacing the breaker.

The 3-pole body takes 6 x 9 mm pitches (54 mm wide), so it occupies three module spaces in a distribution board. IP20 rated, so it's for use inside an enclosure or panel, not in washdown areas.

MPN
MGN25124