Schneider Electric MGN25112 — 2-Pole MCB (DIN Rail)

MGN25112 C60H MCB, 2P D-curve 3 A, 30 kA breaking capacity

MPNMGN25112
Obsolete

Schneider Electric C60H Multi9 miniature circuit breaker, MGN25112, 2-pole, D-curve, 3 A rated current, 30 kA breaking capacity at 240 V AC, thermal-magnetic trip, 35 mm DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN25112 — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
MGN25112 — Electrical
ParameterValue
Rated current [In]3 A at 50 °C conforming to EN/IEC 60947-2
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Network type (AC/DC)AC
Network frequency50/60 Hz
MGN25112 — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu)30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Suitable for isolationYes conforming to EN/IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
MGN25112 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Terminal tightening torquePower circuit: 2 N.m
Comb busbar / distribution block compatibilityTop or bottom: YES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
MGN25112 — Environmental
ParameterValue
Operating temperature range-30...70 °C
Storage temperature range-40...80 °C
MGN25112 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2

Product details

The MGN25112 is a Schneider Electric C60H miniature circuit breaker from the Multi9 range — a 2-pole, D-curve unit rated 3 A, built for distribution duty in 35 mm DIN-rail enclosures. Breaking capacity hits 30 kA Icu at 240 V AC phase-to-phase (15 kA at 415 V, 10 kA at 440 V), which puts it in the C60H tier — high enough for most commercial and light-industrial panelboards where fault current runs under 30 kA.

The 3 A rating is at 50 °C per EN/IEC 60947-2, so no derating is needed at typical panel ambient; above that, the thermal-magnetic trip element adjusts naturally. Service breaking capacity (Ics) is 50 % of Icu — 15 kA at 240 V, 7.5 kA at 415 V, 5 kA at 440 V — meaning after clearing a fault at that level the breaker remains functional, not just safe.

Snaps onto 35 mm symmetrical DIN rail (EN/IEC 60947-2), occupies 4 x 9 mm pitches (36 mm wide) — two-pole width, standard for a 2P MCB in a Multi9 lineup. IP20 finger-safe front; pollution degree 3 per EN/IEC 60947-2, so it's rated for the conductive-dust environment inside a typical panel.

Frequently asked questions

What is the breaking capacity of MGN25112?

30 kA Icu at 240 V AC phase-to-phase, 15 kA at 415 V, and 10 kA at 440 V, all per EN/IEC 60947-2.

MPN