The Schneider Electric MGN25125 is a C60H miniature circuit breaker from the Multi9 range, a 3-pole unit rated 2 A at 50 °C with a D tripping curve. The 30 kA Icu at 240 V AC phase-to-phase (and 15 kA at 415 V, 10 kA at 440 V) tells you it can safely interrupt fault currents up to those levels; below that it stays coordinated with downstream devices per EN/IEC 60947-2 Category A. IP20 finger-safe protection covers the terminal area once installed in an enclosure — standard for panelboard use.
Where it is used and deployment context
This is a distribution-grade miniature circuit breaker for AC networks at 50/60 Hz, rated up to 440 V phase-to-phase. The D curve and 2 A rating suit it for protecting motor circuits, small transformers, or lighting loads with high switch-on surges in a panelboard or sub-distribution board.