Skip to main content
Schneider Electric MGN25129 — Miniature Circuit Breakers (MCB)

MGN25129 C60H MCB, 3P D-curve 10 A, 30 kA breaking

MPNMGN25129
Obsolete

Schneider Electric C60H Multi9 series, MGN25129 miniature circuit breaker, 3-pole D-curve, 10 A rated current, 30 kA breaking capacity at 240 VAC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN25129 — Identification
ParameterValue
Product nameC60
Product rangeMulti9
Product range (series)C60
Product/component typeMiniature circuit-breaker
Device applicationDistribution
MGN25129 — Ratings
ParameterValue
Rated current (In)10 A at 50 °C conforming to EN/IEC 60947-2
Poles configuration3P
Number of protected poles3
Breaking capacity30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity (Ics)15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Rated operational voltage (Ue)440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
MGN25129 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)10000 cycles conforming to EN/IEC 60947-2
Mechanical durability (cycles)20000 cycles
MGN25129 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Control typeToggle
Terminal connection typeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Terminal tightening torquePower circuit: 2 N.m
Wire stripping lengthPower circuit: 14 mm
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width54 mm
Height81 mm
Depth73 mm
Number of 9 mm pitches6
MGN25129 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
Pollution degree3 conforming to EN/IEC 60947-2
MGN25129 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

What this MCB delivers for the panel

The MGN25129 is a C60H miniature circuit breaker from the Multi9 range — a 3-pole, D-curve unit rated 10 A at 50 °C per EN/IEC 60947-2. Breaking capacity is 30 kA Icu at 240 VAC phase-to-phase, stepping down to 15 kA at 415 VAC and 10 kA at 440 VAC — enough headroom for most distribution panels where the upstream transformer or feeder can deliver that fault current. The 3-pole configuration with separate earth-leakage block option means it can serve as the main branch protection in a sub-distribution board, leaving the RCD function to a companion module.

Depth is 73 mm, height 81 mm — fits standard distribution enclosures with adequate wiring space. Tightening torque for power circuit terminals is 2 N·m; strip length 14 mm. No derating needed in typical panel conditions. Ambient operating range -30…70 °C covers most indoor and sheltered outdoor cabinets.

Frequently asked questions

What is the breaking capacity of MGN25129?

The MGN25129 is rated 30 kA Icu at 240 VAC phase-to-phase, 15 kA at 415 VAC, and 10 kA at 440 VAC, all per EN/IEC 60947-2. The service breaking capacity (Ics) is 50 % of those values.

What does the D-curve mean on this MCB?

The D-curve sets the magnetic trip threshold at 12 x In (±20 %), so the breaker tolerates high inrush currents typical of motor loads, small transformers, and discharge lighting without tripping on startup.

What compliance standards does MGN25129 meet?

The MGN25129 is designed and tested to EN/IEC 60947-2 for miniature circuit breakers, with pollution degree 3 and IP20 protection. It carries suitability for isolation and a contact position indicator per that standard.

MPN