Skip to main content
Schneider Electric MGN25126 — Miniature Circuit Breakers (MCB)

MGN25126 C60H MCB, D Curve 3A 3P, 30 kA, Multi9

MPNMGN25126
Obsolete

Schneider Electric C60H Multi9 miniature circuit breaker, MGN25126, D curve, 3 A rated current, 3-pole, 30 kA Icu at 240 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN25126 — Identification
ParameterValue
Product nameC60
Product rangeMulti9
Product range (series)C60
Product/component typeMiniature circuit-breaker
Device applicationDistribution
MGN25126 — Ratings
ParameterValue
Rated current (In)3 A at 50 °C conforming to EN/IEC 60947-2
Poles configuration3P
Number of protected poles3
Breaking capacity30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity (Ics)15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Rated operational voltage (Ue)440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
MGN25126 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)10000 cycles conforming to EN/IEC 60947-2
Mechanical durability (cycles)20000 cycles
MGN25126 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Control typeToggle
Terminal connection typeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Terminal tightening torquePower circuit: 2 N.m
Wire stripping lengthPower circuit: 14 mm
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width54 mm
Height81 mm
Depth73 mm
Number of 9 mm pitches6
MGN25126 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
Pollution degree3 conforming to EN/IEC 60947-2
MGN25126 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The MGN25126 is a Schneider Electric C60H miniature circuit breaker from the Multi9 range, rated 3 A at 50 °C with a D tripping curve. The 3-pole design with thermal-magnetic trip unit handles motor and high-inrush loads where the D curve's 12 x In magnetic threshold avoids nuisance trips on startup.

Mounting & panel fit

Snaps onto 35 mm symmetrical DIN rail. Occupies 6 x 9 mm pitches (54 mm wide), 81 mm tall, 73 mm deep. IP20 finger-safe front, pollution degree 3 rated for industrial control panels.

Breaking capacity & selectivity

Rated Icu of 30 kA at 240 V AC drops to 15 kA at 415 V and 10 kA at 440 V — the voltage derating is steep, so verify the fault level at your system voltage. Ics (service breaking capacity) is 50 % of Icu at each voltage level, meaning the breaker can be reclosed after one fault at that reduced rating. Suitability for isolation confirmed per EN/IEC 60947-2, with a visible contact position indicator.

Frequently asked questions

Where can I buy MGN25126 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock figures or price shown here.

What is the D curve and why does this breaker have it?

The D curve means magnetic tripping occurs at 12 x In (36 A for this 3 A unit), ±20 %. It is selected for loads with high inrush current — motors, transformers, welding equipment — where a B or C curve would nuisance-trip on startup.

What compliance documentation does MGN25126 carry?

Certified to EN/IEC 60947-2 for miniature circuit breakers. Pollution degree 3, IP20 protection. The manufacturer provides the standard declaration of conformity; specific RoHS/REACH statements are available on request at quote time.

MPN
MGN25126