Skip to main content
Schneider Electric SOL80N3E800 — Miniature Circuit Breakers (MCB)

Schneider Electric SOL80N3E800 EasyPact Solar MCCB, 800 A, 5

MPNSOL80N3E800
Active

Schneider Electric EasyPact Solar MCCB, 3P, 800 A, electronic LSI trip, 50 kA at 800 V AC, fixed mount, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

SOL80N3E800 — Identification
ParameterValue
Product range (series)EasyPact Solar MCCB
Product/component typeCircuit breaker
Device applicationDistribution
SOL80N3E800 — Ratings
ParameterValue
Rated current (In)800 A at 40 °C
Poles configuration3P
Rated operational voltage (Ue)800 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated insulation voltage (Ui)1250 V AC conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Overvoltage categoryIII
SOL80N3E800 — Protection
ParameterValue
Trip unit technologyElectronic
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 800 V In
Mechanical durability (cycles)20000 cycles
SOL80N3E800 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
SOL80N3E800 — Environmental
ParameterValue
Operating ambient temperature-20...70 °C
Storage ambient temperature-35...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
SOL80N3E800 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H
SOL80N3E800 — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity50 kA Icu at 800 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ics] rated service short-circuit breaking capacity40 kA at 800 V AC 50/60 Hz conforming to EN/IEC 60947-2
SOL80N3E800 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.25...1 x In
Trip unit protection functionsLSI

Product details

800 A solar-grade MCCB with LSI electronic trip

The Schneider Electric SOL80N3E800 is a 3-pole EasyPact Solar MCCB rated 800 A at 40 °C, with a 50 kA breaking capacity at 800 V AC — that N performance level means it clears faults up to 50 kA without upstream coordination issues in most solar distribution panels. The electronic ETU trip unit gives you LSI protection (long-time, short-time, instantaneous) plus thermal memory, so it tracks real heating in the conductor, not just peak current. Rated operational voltage is 800 V AC 50/60 Hz per EN/IEC 60947-2, with an insulation voltage of 1250 V AC — headroom for high-impedance ground faults common in PV arrays.

Fixed backplate mount, 180 mm wide × 250 mm high × 105 mm deep, with a 40 mm connection pitch. Mounts horizontal or vertical; pollution degree 3 (IEC 60664-1) means it tolerates conductive dust in unsealed enclosures.

Frequently asked questions

Where can I buy SOL80N3E800 and get a price?

The SOL80N3E800 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings for SOL80N3E800?

Rated 800 A at 40 °C, 50 kA breaking capacity at 800 V AC, with an LSI electronic trip unit and 1250 V insulation voltage.

What compliance standards does SOL80N3E800 meet?

Certified to EN/IEC 60947-1, EN/IEC 60947-2, and EN/IEC 60947-2 Annex H. Suitable for isolation per EN/IEC 60947-2.

MPN
SOL80N3E800