Skip to main content
Siemens 3RA1110-1FA15-1AF0 — Motor Starters

Siemens 3RA1110-1FA15-1AF0 SIRIUS Non-Fused Load Feeder

MPN3RA1110-1FA15-1AF0

Siemens SIRIUS 3RA1110-1FA15-1AF0, non-fused load feeder, direct starter, size S00, 1.5 kW at 400 V, snap-on 35 mm DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RA1110-1FA15-1AF0 — Identification
ParameterValue
Product designationnon-fused load feeder
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructiondirect starter
Included contactor (type)3RT1015-1AF01
Included circuit-breaker (type)3RV1011-1FA10
Included link module (type)3RA1911-1AA00
Reference designation (IEC 81346-2)Q
3RA1110-1FA15-1AF0 — Ratings & Performance
ParameterValue
Rated motor power at 400 V1.5 kW
Operational current Ie, AC-3 at 400 V3.6 A
Rated impulse withstand voltage (Uimp)6 kV
Mechanical service life, typ. (switching cycles)30 000 000
3RA1110-1FA15-1AF0 — Protection & Tripping
ParameterValue
Short-circuit protectionYes
Overload release setting range (current)3.5 ... 5 A
Duty / utilization type (IEC 60947-6-2)1
3RA1110-1FA15-1AF0 — Contacts & Control
ParameterValue
Rated voltage range at 50 Hz110 V
Control supply voltage typeAC
Auxiliary contacts, NO1
Auxiliary switch extensionYes
Switching contact typeelectromechanical
3RA1110-1FA15-1AF0 — Communication
ParameterValue
AS-Interface protocol supportNo
3RA1110-1FA15-1AF0 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (18 ... 14)
Mounting / fastening methodsnap-on fastening on 35 mm standard rail
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Width45 mm
Height159 mm
Depth75 mm
3RA1110-1FA15-1AF0 — Environmental
ParameterValue
Operating temperature range-20 ... +70 °C
Storage temperature range-55 ... +80 °C
Pollution degree3

Product details

The Siemens 3RA1110-1FA15-1AF0 is a SIRIUS non-fused load feeder configured as a direct starter, size S00, rated 1.5 kW at 400 V. It arrives as a pre-assembled combination of a 3RT1015-1AF01 contactor, a 3RV1011-1FA10 circuit breaker for short-circuit protection, and a 3RA1911-1AA00 link module — all on a 45 mm wide footprint that snaps onto a 35 mm standard rail. This is a self-contained motor-starting and protection package for a single three-phase load up to 1.5 kW at 400 V. The direct-starter design means the contactor closes straight across the line — no reduced-voltage starting. The supplied circuit breaker provides the short-circuit protection, so the feeder is non-fused: no separate fuse holders or fuse links to stock. The 1.5 kW rating at 400 V tells you the maximum motor size this feeder can switch in AC-3 duty; size S00 is the smallest frame in the SIRIUS family, suited for light-duty pumps, fans, and conveyors.

Dimensions: 45 mm wide, 159 mm high, 75 mm deep. Clearance requirements: 20 mm upward, 10 mm forward, 9 mm backward, 0 mm downward, 20 mm at the side. Shock resistance is 9.8 g. Conductor cross-sections accepted: solid or stranded 0.5 to 4 mm², and 2x (0.75 to 2.5 mm²) for daisy-chaining. AWG equivalents for main contacts: 2x (18 to 14). The product extension for auxiliary switches is available (product extension auxiliary switch: Yes), so you can add feedback contacts without modifying the feeder body. No bus communication is built in (PROFINET: No, PROFIBUS DP: No, product function bus communication: No) — this is a standalone electromechanical feeder, not a networked motor starter.

Frequently asked questions

What is the replacement for 3RA1110-1FA15-1AF0?

Buyers need to know the exact successor (SIRIUS 3RA2) to continue their design or maintenance without compatibility risks.

Is 3RA1110-1FA15-1AF0 obsolete or phased out?

Lifecycle status directly affects purchasing decisions: if phased out, buyers must plan for last-time buy or immediate switch to replacement.

What are the specifications of 3RA1110-1FA15-1AF0 (voltage, current, coil)?

Design engineers and maintenance techs need exact ratings to validate fit in their circuit before purchase.

Can I use 3RA2 as a direct replacement for 3RA1110 without modification?

Buyers often need to know if the successor is drop-in compatible (same mounting, connections, ratings) to avoid re-engineering.

Where can I buy 3RA1110-1FA15-1AF0 in stock?

Sourcing buyers need immediate availability from distributors to fill BOM lines or replace failed units quickly.

What is the price of 3RA1110-1FA15-1AF0 vs its successor 3RA2?

Cost comparison influences whether buyers choose to buy remaining stock of old part or switch to new series.

MPN
3RA1110-1FA15-1AF0