What this SIRIUS reversing starter is
Rated at 1.5 kW at 400 V, it is designed for small three-phase induction motors on conveyor drives, pump reversals, or any application needing forward/reverse control from a single panel-mounted unit. The kit includes a 3RT10 15-1AP02 contactor, a 3RV10 11-1FA10 circuit-breaker, a 3RA19 11-1AA00 link module, and a 3RA19 13-1D RS assembly kit — all pre-configured to coordinate, so you don't have to size each component separately.
Mounting and wiring in the panel
Snaps directly onto 60 mm busbar systems (center-to-center spacing 60 mm), which is the standard for SIRIUS S00 feeders — no DIN rail adapter needed if you're feeding from a busbar. Mounts horizontally only, with clearance: 20 mm upwards, 10 mm forwards, 9 mm backwards, 0 mm downwards, and 20 mm at the side. That 0 mm downwards means you can stack units tight vertically — handy when squeezing multiple starters into a narrow column. Wiring terminals accept solid or stranded 0.5 to 4 mm² (2x 0.75 to 2.5 mm² for the main contacts), or 2x AWG 18 to 14.