Factory-integrated components — one order code, no separate picking
The 3RA2110-0DD15-1AP6 ships as a complete assembled unit: the supplied contactor is 3RT2015-1AP61, the link module is 3RA1921-1DA00, the busbar adapter is 8US1251-5DS10, and the circuit-breaker is 3RV2011-0DA10. No separate ordering or field assembly of these subcomponents is needed. The overload release is thermal bimetallic (Class 10 trip class), the switching contact is electromechanical, and the short-circuit trip is magnetic. This combination provides standard motor protection for general-purpose induction motors up to the S00 frame size.
Panel fit and clearance — tight integration possible
Width is 45 mm, depth 155.1 mm, height 200 mm — the S00 form factor fits standard 60 mm busbar systems via the snap-on fastening method. Mounting position is vertical only. Clearance spaces: 20 mm upwards, 0 mm forwards and backwards, 10 mm downwards, 9 mm at the side. The zero forward/backward clearance means the unit can be placed flush against adjacent devices or enclosure walls, saving panel depth.
Voltage ratings and control supply
Rated insulation voltage is 690 V, with AC-3 switching duty rated at 690 V maximum. This provides headroom for 400/480 V systems and supports 690 V industrial networks common in mining, pumping, and heavy conveyor applications. The operating frequency range is 50/60 Hz, matching global line frequencies.
Environmental and wiring limits
Operating temperature range is -20 to +60 °C; transport range is -55 to +80 °C; storage range is -50 to +80 °C. Pollution degree 3 means the unit is rated for industrial environments with conductive contamination — no additional conformal coating required for typical panel conditions. Assignment type 2 (coordination type 2) ensures the starter withstands short-circuit faults without damage to the contactor or overload relay.