SIRIUS direct starter, S00 frame, busbar-mounted
The 3RA2110-0DH15-1AP0: The supplied contactor is 3RT2015-2AP01 and the link module is 3RA2911-2AA00, so the assembly arrives as a matched set with coordinated overload protection.
Ratings and thermal limits for panel integration
The operating temperature range is -20 to +60 °C, with storage and transport limits of -50 to +80 °C; the vertical mounting position is specified, and the required clearances are 50 mm upward, 20 mm forward, 20 mm at the side, 10 mm downward, and 0 mm backward. Dimensions are 155 mm depth, 45 mm width, and 260 mm height — the 45 mm width matches the S00 busbar footprint, so it occupies one slot on a 60 mm busbar system.
The substance prohibitance date of 10/01/2009 indicates RoHS compliance per the EU directive, and the SIRIUS series carries CE and UL certifications typical for industrial control panels.