90 kW at 400 V — SIRIUS S00 direct starter
The 3RA2110-0ED15-1FB4: It ships as a pre-assembled unit: the supplied contactor (3RT2015-1FB41), thermal bimetallic overload relay, and magnetic short-circuit trip are integrated with a link module (3RA1921-1DA00) and a busbar adapter (8US1251-5DS10) for snapping onto 60 mm busbar systems.
Class 10 overload and panel fit
The thermal bimetallic overload is set to Trip Class 10, meaning it protects standard AC induction motors during start-up without nuisance tripping on normal inrush — a common spec for general-purpose motor branches. Dimensions are 155 mm deep, 45 mm wide, 203 mm tall, with a vertical mounting position and clearance requirements of 50 mm upward, 20 mm forward, 20 mm at the side, and 10 mm downward — zero backward clearance needed, so it fits tight against the backplane.