Skip to main content
Siemens 3RA2110-0FA15-1AP6 — Motor Starters

Siemens 3RA2110-0FA15-1AP6 SIRIUS Motor Starter, Size S00

MPN3RA2110-0FA15-1AP6

Siemens SIRIUS 3RA2110-0FA15-1AP6 non-fused motor starter, Size S00, direct starter, 120 W rated power at 400 V, Class 10 trip class, 45 mm width, snap-on DIN rail mount.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA2110-0FA15-1AP6 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructiondirect starter
Circuit-breaker sizeS00
Included contactor (type)3RT2015-1AP61
Included circuit-breaker (type)3RV2011-0FA10
Included link module (type)3RA1921-1DA00

Ratings & Performance

3RA2110-0FA15-1AP6 — Ratings & Performance
ParameterValue
Rated motor power at 400 V120 W
Operational current Ie, AC-3 at 400 V0.4 A
Rated voltage at AC-3, max.690 V
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)30 000 000

Protection & Tripping

3RA2110-0FA15-1AP6 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)0.35 ... 0.5 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2

Contacts & Control

3RA2110-0FA15-1AP6 — Contacts & Control
ParameterValue
Rated value690 V
Rated voltage range at 50 Hz187 ... 242 V
Auxiliary contacts, NO1
Auxiliary contacts, NC0
Auxiliary switch extensionYes
Switching contact typeelectromechanical

Mechanical & Connection

3RA2110-0FA15-1AP6 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
Mounting / fastening methodSnap-mounted to DIN rail or screw-mounted with additional push-in lug
Mounting positionvertical
Width45 mm
Height167.2 mm
Depth97.1 mm

Environmental

3RA2110-0FA15-1AP6 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

The 3RA2110-0FA15-1AP6 is a Siemens SIRIUS non-fused motor starter, assembled as a direct starter in Size S00. It ships as a factory-matched set: the 3RT2015-1AP61 contactor, the 3RV2011-0FA10 circuit-breaker, and the 3RA1921-1DA00 link module, all pre-configured for a Type 2 coordination. Rated motor power is 120 W at 400 V, 180 W at 500 V, and 250 W at 690 V. The overload release is thermal bimetallic; the short-circuit release is magnetic. This combination provides both overload protection (heating curve) and instantaneous magnetic trip for fault currents. The contactor is electromechanical, rated for AC-3 switching duty up to 690 V.

Mounting and panel integration — 45 mm width, DIN rail snap-on

Width is 45 mm, depth 97.1 mm, height 167.2 mm. The unit snaps onto a DIN rail or can be screw-mounted with an additional push-in lug. Mounting position is vertical. Required clearances: 20 mm upward, 10 mm downward, 9 mm at the side, 0 mm forward and backward. These gaps allow airflow for the thermal overload and arc-fault venting from the circuit-breaker. In a crowded panel, the 45 mm width per feeder keeps the density reasonable for Size S00. AWG equivalents are 2× (20 to 16), 2× (18 to 14), or 2× 12. The auxiliary switch can be field-added.

Coil voltage and environmental ratings

This covers nominal 208–240 V supplies with tolerance. Rated insulation voltage is 690 V; surge voltage resistance is 6 kV. Ambient operating range is -20 to +60 °C; storage range is -50 to +80 °C; transport range is -55 to +80 °C. Pollution degree 3 means the unit is rated for industrial environments with conductive pollution.

Sourcing and lifecycle — current production, quoted to order

The 3RA2 series is the standard SIRIUS non-fused motor starter line; the Size S00 frame covers the lower power range up to approximately 250 W at 690 V.

Frequently asked questions

What is the rated motor power of 3RA2110-0FA15-1AP6 at 400 V?

Rated motor power is 120 W at 400 V, 180 W at 500 V, and 250 W at 690 V. These values apply for AC-3 duty.

What components are supplied with the 3RA2110-0FA15-1AP6 motor starter?

The assembly includes the 3RT2015-1AP61 contactor, the 3RV2011-0FA10 circuit-breaker, and the 3RA1921-1DA00 link module, factory-configured for Type 2 coordination.

What is the width and mounting method of the 3RA2110-0FA15-1AP6?

Width is 45 mm, depth 97.1 mm, height 167.2 mm. It snaps onto a DIN rail or can be screw-mounted with an additional push-in lug. Mounting position is vertical.

What compliance documentation does Siemens provide for 3RA2110-0FA15-1AP6?

Full compliance documentation (RoHS, REACH, UL, IEC) is available from Siemens per their standard declarations for the SIRIUS 3RA2 series.

MPN
3RA2110-0FA15-1AP6