Size S00 non-fused motor starter — what it packs
The 3RA2110-0GA15-1AP6: This is a Siemens SIRIUS 3RA2 non-fused motor starter, a direct starter combining a contactor and a thermal bimetallic overload relay in one unit. It ships with the contactor 3RT2015-1AP61 and the circuit breaker 3RV2011-0GA10 already linked via a link module 3RA1921-1DA00. The operating frequency range is 50 to 60 Hz. The short-circuit trip is magnetic, providing fast clearing on high faults.
Panel fit — 45 mm wide, snap-on DIN rail
Width is 45 mm, depth 97.1 mm, height 167.2 mm — size S00 footprint. Snap-mounts onto DIN rail or can be screw-mounted with an additional push-in lug. Mounting position is vertical. Clearance requirements: 20 mm upwards, 10 mm downwards, 9 mm at the side. No forward or backward clearance needed. This fits tightly in a standard 600 mm deep enclosure with room for wiring ducts. Operating temperature range -20 to +60 °C, storage -50 to +80 °C. Pollution degree 3, surge voltage resistance 6 kV — suitable for industrial control panels with moderate contamination.
Supplied as a complete starter assembly: contactor, overload relay, and circuit breaker pre-linked. The auxiliary switch option is available (product extension auxiliary switch: Yes).