Skip to main content
Siemens 3RA2110-0GD15-1BB4 — Motor Starters

Siemens 3RA2110-0GD15-1BB4 SIRIUS DOL Starter, S00

MPN3RA2110-0GD15-1BB4
Active

Siemens SIRIUS direct-on-line starter, 3RA2110-0GD15-1BB4, size S00, 180 W at 400 V, CLASS 10, for 60 mm busbar systems.

StockContact for availability
Lead time3-5 Days wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA2110-0GD15-1BB4 — Identification
ParameterValue
Product designationDirect (on-line) starter
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructionfor 60 mm busbars
Circuit-breaker sizeS00
Included contactor (type)3RT2015-1BB41
Included circuit-breaker (type)3RV2011-0GA10
Included link module (type)3RA1921-1DA00

Ratings & Performance

3RA2110-0GD15-1BB4 — Ratings & Performance
ParameterValue
Rated motor power at 400 V180 W
Operational current Ie, AC-3 at 400 V0.6 A
Rated voltage at AC-3, max.690 V
Rated current at 480 V0.63 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)30 000 000

Protection & Tripping

3RA2110-0GD15-1BB4 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)150 000 A
Overload release setting range (current)0.45 ... 0.63 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2

Contacts & Control

3RA2110-0GD15-1BB4 — Contacts & Control
ParameterValue
Rated value24 ... 24 V
Control supply voltage typeDC
Auxiliary switch extensionYes
Switching contact typeelectromechanical

Communication

3RA2110-0GD15-1BB4 — Communication
ParameterValue
AS-Interface protocol supportNo

Mechanical & Connection

3RA2110-0GD15-1BB4 — Mechanical & Connection
ParameterValue
Main contact conductor range (AWG)2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
Mounting / fastening methodfor snapping onto 60 mm busbar systems
Mounting positionvertical
Width45 mm
Height200 mm
Depth155 mm

Environmental

3RA2110-0GD15-1BB4 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-50 ... +80 °C
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

What this starter package includes — and what it saves you wiring

The 3RA2110-0GD15-1BB4 is a Siemens SIRIUS direct-on-line starter, size S00, pre-configured for snapping onto 60 mm busbar systems — it ships as a coordinated assembly with the contactor (3RT2015-1BB41), link module (3RA1921-1DA00), busbar adapter (8US1251-5DS10), and circuit-breaker (3RV2011-0GA10) already matched. That means one order code gets you the motor branch circuit protection, switching, and overload protection in a single DIN-rail-compatible footprint — no separate breaker, contactor, and overload relay to select and interconnect.

Motor ratings and trip class — what the numbers mean for a real load

Rated motor power is 180 W at 400 V, 50-60 Hz, with a full-load current of 0.63 A at 480 V — this is a fractional-horsepower starter for small pumps, fans, conveyors, or valve actuators.

Mounting and clearances — fitting this into a panel or busbar system

The starter snaps onto 60 mm busbar systems (vertical mounting position only) and measures 155 mm deep × 45 mm wide × 200 mm tall — the S00 feeder size keeps the panel fill factor tight. Required clearances: 50 mm above, 20 mm forward, 0 mm behind, 10 mm below, and 20 mm to the side — the zero rear clearance means it can sit flush against a backplate, but the forward clearance matters for the busbar adapter and wiring access.

Environmental limits and compliance paperwork

Operating temperature range is -20 to +60 °C, with storage and transport limits of -50 to +80 °C — adequate for most indoor panel environments but check the ambient near ovens or freezers. The overload release includes temperature compensation across the -20 to +60 °C operating range, so the trip curve stays stable without manual adjustment when the panel warms up.

Sourced through independent industrial distribution; availability and volume pricing confirmed at RFQ against the BOM quantity. No minimum order quantity is assumed — quoted per project need. The supplied contactor (3RT2015-1BB41), link module (3RA1921-1DA00), busbar adapter (8US1251-5DS10), and circuit-breaker (3RV2011-0GA10) are all standard SIRIUS catalog items, so replacement parts are available individually if a component fails in the field.

Frequently asked questions

What components are included with this starter?

The 3RA2110-0GD15-1BB4 ships as a coordinated assembly including the contactor (3RT2015-1BB41), link module (3RA1921-1DA00), busbar adapter (8US1251-5DS10), and circuit-breaker (3RV2011-0GA10) — all pre-matched for the S00 frame.

What is the motor power rating of this starter?

Rated motor power is 180 W at 400 V, 50-60 Hz, with a full-load current of 0.63 A at 480 V. The maximum switching voltage in AC-3 duty is 690 V.

MPN
3RA2110-0GD15-1BB4