Direct starter, size S00, 0.63 A AC-3 — what it fits
The 3RA2110-0GH15-1AP0: It ships as a pre-assembled unit: the supplied contactor is 3RT2015-2AP01 and the link module is 3RA2911-2AA00, so the wiring between the contactor and the overload relay is already integrated. The CLASS 10 trip curve means it will open within 10 seconds at 600 % of the set current — fast enough to protect standard squirrel-cage motors without nuisance tripping on start-up.
Mounting and wiring — snaps onto 60 mm busbars
This starter is designed for snapping onto 60 mm busbar systems, not DIN rail — the fastening method and product design both call out the 60 mm busbar footprint, so verify the panel infrastructure before specifying. The main current circuit uses spring-loaded terminals — push-in wiring for solid or ferruled stranded conductors, no screw torque to check. Dimensions are 155 mm deep, 45 mm wide, 260 mm tall. Mounting position is vertical, with clearance requirements: 50 mm upwards, 20 mm forwards, 10 mm downwards, 20 mm at the side, and 0 mm backwards.