What this SIRIUS load feeder delivers
The 3RA2110-1ED15-1AK6 is a SIRIUS non-fused load feeder, size S00, configured as a direct starter — meaning it combines a contactor and overload relay in one pre-assembled unit for straightforward motor on/off control. It ships with the 3RT2015-1AK61 contactor and 3RA1921-1DA00 link module already matched, so there is no separate component selection or wiring between the contactor and overload block.
Voltage and power coverage across global line voltages
Motor power ratings span 0.75 hp at 200/208 V up to 3 hp at 575/600 V, and 1 500 W at 400 V up to 3 000 W at 690 V — covering common North American and IEC line voltages.
Panel fit and mounting
Width is 45 mm, depth 155.1 mm, height 200 mm — the 45 mm width fits standard 45 mm-wide DIN-rail or busbar mounting footprints, and the unit snaps onto 60 mm busbar systems without additional brackets. Mounting position is vertical only, with 20 mm clearance required above and 10 mm below for airflow and wiring access.