Rated motor power across common line voltages
The 3RA2110-1FA15-1AP6: At 400 V the rated power is 1 500 W (roughly 2 hp), and at 230 V it's 0.5 hp. These are AC-3 duty ratings, so the starter switches motor loads up to those currents during starting and running.
Overload protection: thermal bimetallic, Class 10
The overload release is thermal bimetallic — it tracks motor heating via a bimetal strip, not electronics. That's standard for general-purpose motor starting (conveyors, pumps, fans) where the start time is under a few seconds. For high-inertia loads with longer acceleration, a Class 20 or Class 30 trip curve would be needed.
Mounting and panel space
Dimensions: 45 mm wide, 167.2 mm tall, 97.1 mm deep. The S00 frame size is the smallest in the SIRIUS 3RA2 family — fits a standard 45 mm-wide DIN slot. Mounting position must be vertical; derating applies if tilted. Clearance: 20 mm upward, 10 mm downward, 9 mm to the side, zero forward or backward.
Supplied components and wiring
The starter ships with the contactor (3RT2015-1AP61) and the link module (3RA1921-1DA00) pre-assembled — no separate ordering of the contactor and overload relay. The direct-starter design means the contactor and overload are wired in series internally; you connect line and load directly to the main terminals.