Active production — what it means for the BOM line
The 3RA2110-1FD15-1AP6: It's a SIRIUS-branded non-fused motor starter (direct starter design), size S00, built around a supplied 3RT2015-1AP61 contactor and a 3RA1921-1DA00 link module. The overload release is thermal bimetallic, trip class 10.
Rated power across common line voltages
At 400 V AC-3 it's rated 1500 W; at 460/480 V it's 3 hp. The 690 V maximum rated value (AC-3) covers 600 V class installations without derating the switching capacity. At 230 V it's rated 0.5 hp; at 200/208 V it's 1 hp.
Mounting and panel fit — snaps onto 60 mm busbar
Fastening method is snap-on for 60 mm busbar systems — no DIN rail adapter needed if you're running a busbar grid. Mounting position is vertical only. Dimensions: 45 mm wide, 200 mm tall, 155.1 mm deep. Clearance requirements: 20 mm upwards, 10 mm downwards, 9 mm at the side. The S00 footprint is compact enough for high-density panel layouts. Pollution degree 3 — suitable for industrial environments with conductive dust or condensation.
Operating temperature range -20 to +60 °C; storage -50 to +80 °C; transport -55 to +80 °C. The wide storage range means it can sit on a shelf in an unheated warehouse without issue.