Skip to main content
Siemens 3RA2110-1HD16-1AP6 — Motor Starters

Siemens 3RA2110-1HD16-1AP6 Motor Starter, S00, 690 V

MPN3RA2110-1HD16-1AP6

Siemens SIRIUS 3RA2110-1HD16-1AP6 non-fused motor starter, S00 size, direct starter design, 690 V AC-3 rated, Class 10 trip, 45 mm width.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA2110-1HD16-1AP6 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructiondirect starter
Circuit-breaker sizeS00
Included contactor (type)3RT2016-1AP61
Included circuit-breaker (type)3RV2011-1HA10
Included link module (type)3RA1921-1DA00

Ratings & Performance

3RA2110-1HD16-1AP6 — Ratings & Performance
ParameterValue
Rated motor power at 400 V3 000 W
Operational current Ie, AC-3 at 400 V6.5 A
Rated voltage at AC-3, max.690 V
Rated motor power at 460/480 V (hp)5 hp
Rated motor power at 575/600 V (hp)5 hp
Rated current at 480 V7.6 A
Rated current at 600 V6.33 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)30 000 000

Protection & Tripping

3RA2110-1HD16-1AP6 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)5.5 ... 8 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)1

Contacts & Control

3RA2110-1HD16-1AP6 — Contacts & Control
ParameterValue
Rated value690 V
Rated voltage range at 50 Hz187 ... 242 V
Auxiliary contacts, NO1
Auxiliary contacts, NC0
Auxiliary switch extensionYes
Switching contact typeelectromechanical

Mechanical & Connection

3RA2110-1HD16-1AP6 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
Mounting / fastening methodfor snapping onto 60 mm busbar systems
Mounting positionvertical
Width45 mm
Height200 mm
Depth155.1 mm

Environmental

3RA2110-1HD16-1AP6 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

What this SIRIUS starter carries

The Siemens 3RA2110-1HD16-1AP6 is a non-fused motor starter from the SIRIUS 3RA2 series, size S00, configured as a direct starter. It ships with a 3RT2016-1AP61 contactor and a 3RA1921-1DA00 link module, so the assembly is a single order-code line item that mates the contactor and overload relay on the factory-supplied busbar interface.

Dimensional fit and mounting constraints

The footprint is 45 mm wide by 200 mm tall by 155.1 mm deep, with a vertical mounting position specified. It fastens by snapping onto 60 mm busbar systems — no DIN-rail adapter needed if the panel uses the standard 60 mm centre-centre busbar pitch. Clearance requirements: 20 mm upwards, 10 mm downwards, 9 mm at the side, and zero forwards or backwards. That zero forward clearance means the front face can sit flush against a panel door or adjacent component without additional air gap, provided the busbar system provides the vertical support.

Environmental and wiring limits

Pollution degree 3 means it tolerates conductive dust and occasional condensation — typical for industrial control panels not in a sealed cleanroom. The S00 frame size limits the lug width — stay within the 4 mm² maximum to close the terminal cover.

Frequently asked questions

What clearance is needed around the 3RA2110-1HD16-1AP6 in a panel?

Allow 20 mm above, 10 mm below, and 9 mm at the side; no forward or backward clearance is required.

MPN
3RA2110-1HD16-1AP6