AC-3 current and motor load envelope
The 3RA2110-1JE16-1BB4: At 480 V the rating is 7.6 A, which matches a 5 hp motor at 460/480 V; at 600 V the same 7.6 A supports a 7.5 hp motor at 575/600 V. No PROFIsafe or PROFINET protocol on this variant; it is a hard-wired, non-networked direct starter.
Mounting and terminal integration
The envelope is 97 mm deep × 45 mm wide × 198 mm high — the 45 mm width occupies one standard DIN module. Clearance requirements: 50 mm above, 20 mm below, 20 mm at the sides, 20 mm forward, 0 mm rearward. Main circuit connections are spring-loaded terminals — no screw torque verification needed during commissioning, which reduces installation time on multi-starter panels. The supplied contactor is 3RT2016-2BB41 and the link module is 3RA2911-2AA00; these are the sub-assembly order codes for traceability in the BOM.