Skip to main content
Siemens 3RA2110-1KA17-1AP6 — Motor Starters

Siemens 3RA2110-1KA17-1AP6 SIRIUS Motor Starter, 11 A, 690 V

MPN3RA2110-1KA17-1AP6

Siemens SIRIUS 3RA2110-1KA17-1AP6 non-fused motor starter, Size S00, direct starter, 11 A at 480 V, 5.5 kW at 400 V, Class 10, thermal bimetallic overload, 690 V max, DIN rail.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA2110-1KA17-1AP6 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructiondirect starter
Circuit-breaker sizeS00
Included contactor (type)3RT2017-1AP61
Included circuit-breaker (type)3RV2011-1KA10
Included link module (type)3RA1921-1DA00

Ratings & Performance

3RA2110-1KA17-1AP6 — Ratings & Performance
ParameterValue
Rated motor power at 400 V5 500 W
Operational current Ie, AC-3 at 400 V11.5 A
Rated voltage at AC-3, max.690 V
Rated motor power at 460/480 V (hp)7.5 hp
Rated motor power at 575/600 V (hp)10 hp
Rated current at 480 V11 A
Rated current at 600 V11 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)30 000 000

Protection & Tripping

3RA2110-1KA17-1AP6 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)9 ... 12.5 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)1

Contacts & Control

3RA2110-1KA17-1AP6 — Contacts & Control
ParameterValue
Rated value690 V
Rated voltage range at 50 Hz187 ... 242 V
Auxiliary contacts, NO1
Auxiliary contacts, NC0
Auxiliary switch extensionYes
Switching contact typeelectromechanical

Mechanical & Connection

3RA2110-1KA17-1AP6 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
Mounting / fastening methodSnap-mounted to DIN rail or screw-mounted with additional push-in lug
Mounting positionvertical
Width45 mm
Height167.2 mm
Depth97.1 mm

Environmental

3RA2110-1KA17-1AP6 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

Panel integration — DIN rail footprint and wiring

The 3RA2110-1KA17-1AP6: The supplied link module 3RA1921-1DA00 connects the contactor coil to the overload relay, and the supplied contactor 3RT2017-1AP61 handles the switching — no separate ordering of subcomponents for this assembly.

Duty ratings and thermal environment

The thermal bimetallic overload release provides motor protection based on heating and cooling curves — it tracks the motor's thermal state more closely than a fixed electronic curve for frequent start-stop cycles. Degree of pollution 3 means the unit is rated for conductive pollution environments typical of control panels in industrial settings — no additional conformal coating needed for normal factory air.

MPN
3RA2110-1KA17-1AP6