Panel footprint and mounting constraints
The 3RA2115-0CD15-1AK6 is a SIRIUS non-fused motor starter in size S00, designed as a direct starter with a thermal bimetallic overload release and a magnetic short-circuit trip. It occupies 45 mm width, 200 mm height, and 155.1 mm depth on the DIN rail, and is intended for snapping onto 60 mm busbar systems. Mounting position is vertical, with required clearances of 20 mm upwards, 10 mm downwards, and 9 mm at the side; no forward or backward clearance is needed.
Rated duty and trip coordination
The control circuit accepts 93.5…121 V at 50 Hz or 96…132 V at 60 Hz, with power consumption ranging from 60 W at 400 V to 120 W at 690 V.
Supplied components and wiring
The unit ships as a pre-assembled combination: a 3RT2015-1AK61 contactor, a 3RA1921-1DA00 link module, a 3RV2011-0CA15 circuit-breaker, and a 8US1251-5DS10 busbar adapter. AWG equivalents are 2x (20…16) and 2x (18…14) for the contactor. An auxiliary switch extension is available as a product option, allowing feedback or status signalling without additional external relays.