Siemens SIRIUS 3RA2115-0EA15-1AP6 non-fused motor starter, Size S00, direct starter, CLASS 10 thermal bimetallic overload, 3-pole, 690 V AC-3 max, 45 mm width, snap-on DIN rail.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA2115-0EA15-1AP6 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructiondirect starter
Circuit-breaker sizeS00
Included contactor (type)3RT2015-1AP61
Included circuit-breaker (type)3RV2011-0EA15
Included link module (type)3RA1921-1DA00

Ratings & Performance

3RA2115-0EA15-1AP6 — Ratings & Performance
ParameterValue
Rated motor power at 400 V90 W
Operational current Ie, AC-3 at 400 V0.3 A
Rated voltage at AC-3, max.690 V
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V

Protection & Tripping

3RA2115-0EA15-1AP6 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)0.28 ... 0.4 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2

Contacts & Control

3RA2115-0EA15-1AP6 — Contacts & Control
ParameterValue
Rated value690 V
Rated voltage range at 50 Hz187 ... 242 V
Auxiliary contacts, NO2
Auxiliary contacts, NC1
Auxiliary switch extensionYes
Switching contact typeelectromechanical

Mechanical & Connection

3RA2115-0EA15-1AP6 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Mounting / fastening methodSnap-mounted to DIN rail or screw-mounted with additional push-in lug
Mounting positionvertical
Width45 mm
Height167.2 mm
Depth97.1 mm

Environmental

3RA2115-0EA15-1AP6 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

What this SIRIUS motor starter packs

The 3RA2115-0EA15-1AP6 is a SIRIUS non-fused motor starter — a direct starter meaning the contactor and overload relay come as a single, pre-assembled unit. It's built in Size S00, which is the smallest frame in the SIRIUS family, so it fits tight panel layouts. It ships with a 3RT2015-1AP61 contactor and a 3RV2011-0EA15 circuit breaker already linked by a 3RA1921-1DA00 link module. That means you're not piecing together three separate catalog numbers — it arrives as one assembly ready to wire. The overload release is thermal bimetallic, CLASS 10 trip class. That's fast enough to protect a motor during a stall without nuisance-tripping on normal startup inrush.

Mounting and panel fit — the dimensions that matter

At 45 mm wide and 97.1 mm deep, this starter takes up one standard modular DIN space. Height is 167.2 mm. It snaps onto a DIN rail or can be screw-mounted with an additional push-in lug — the fastening method gives you options if the panel layout is tight. Clearance requirements: you need 20 mm above, 10 mm below, and 9 mm to the side. No clearance needed forward or backward. That 20 mm upward gap is for the arc chute ventilation — don't skimp on it or the contactor may not cool properly under sustained load. Mounting position is vertical only. If you lay it sideways, the bimetallic overload won't track motor heating the same way — the datasheet derating assumes upright orientation.

Electrical ratings — what they mean for motor control

Rated for AC-3 duty up to 690 V maximum, 3 poles for the main current circuit. AC-3 is the standard category for squirrel-cage motors: switching during running, occasional inrush on start. Power dissipation at rated load: 90 W at 400 V, 120 W at 500 V, 180 W at 690 V. That heat goes into the panel — if you're packing several starters in a row, factor this into your thermal calculation so the cabinet doesn't cook. Operating frequency is 50/60 Hz, coil voltage range 187–242 V at 50 Hz and 192–264 V at 60 Hz. That covers nominal 208–240 V control supplies with enough tolerance for brownout conditions. Surge voltage resistance rated at 6 kV, degree of pollution 3. That means it's built for industrial environments where conductive dust or humidity is present — not just clean control rooms.

Environmental limits and storage

Operating temperature range is -20 to +60 °C. Storage range is -50 to +80 °C, transport range -55 to +80 °C. If this starter sits in an unheated warehouse over winter, those storage limits tell you it's fine down to -50 °C as long as it's not powered.

MPN