Skip to main content
Siemens 3RA2115-0EA16-2BB4-ZX95 — Motor Starters

Siemens 3RA2115-0EA16-2BB4-ZX95 SIRIUS DOL Starter

MPN3RA2115-0EA16-2BB4-ZX95
Active

Siemens SIRIUS 3RA2115-0EA16-2BB4-ZX95 direct-on-line motor starter, Size S00, 90 kW at 400 V AC-3, Class 10 thermal overload, 24 V DC coil, screw terminals, 45 mm wide, DIN rail mount.

StockContact for availability
Lead time3-5 Days wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA2115-0EA16-2BB4-ZX95 — Identification
ParameterValue
Product designationDirect (on-line) starter
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructionfor standard rail or screw mounting
Circuit-breaker sizeS00
Included contactor (type)3RT2016-1BB42
Included circuit-breaker (type)3RV2011-0EA15
Included link module (type)3RA1921-1DA00

Ratings & Performance

3RA2115-0EA16-2BB4-ZX95 — Ratings & Performance
ParameterValue
Rated motor power at 400 V90 kW
Rated voltage at AC-3, max.690 V
Rated current at 480 V0.4 A
Rated current at 600 V0.4 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V

Protection & Tripping

3RA2115-0EA16-2BB4-ZX95 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)150 000 A
Overload release setting range (current)0.28 ... 0.4 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2

Contacts & Control

3RA2115-0EA16-2BB4-ZX95 — Contacts & Control
ParameterValue
Rated value24 ... 24 V
Control supply voltage typeDC
Auxiliary contacts, NO1
Auxiliary contacts, NC1
Auxiliary switch extensionYes
Switching contact typeelectromechanical

Communication

3RA2115-0EA16-2BB4-ZX95 — Communication
ParameterValue
AS-Interface protocol supportNo

Mechanical & Connection

3RA2115-0EA16-2BB4-ZX95 — Mechanical & Connection
ParameterValue
Mounting / fastening methodscrew and snap-on mounting onto 35 mm DIN rail
Mounting positionvertical
Width45 mm
Height167 mm
Depth97 mm

Environmental

3RA2115-0EA16-2BB4-ZX95 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-50 ... +80 °C
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

What this DOL starter delivers on a motor branch

The 3RA2115-0EA16-2BB4-ZX95 is a SIRIUS direct-on-line starter — a pre-assembled combination of contactor, overload relay, and circuit breaker in one Size S00 footprint.

Panel fit and mounting constraints

The mounting position is vertical, and the enclosure must allow 50 mm clearance above and 20 mm forward for ventilation and arc containment — no clearance needed at the back. The link module 3RA1921-1DA00 connects the contactor and breaker internally, reducing wiring time on the panel build.

Coil voltage and control compatibility

The control coil is rated 24 V DC — a standard PLC output voltage for industrial control panels. No PROFIsafe or PROFINET IO protocol is integrated; this is a conventional electromechanical starter with a magnetic short-circuit trip and thermal overload. Operating frequency is 50/60 Hz, so the same unit works on 50 Hz or 60 Hz line supplies without derating the motor power rating.

MPN