Skip to main content
Siemens 3RA2115-0ED15-1AP6 — Motor Starters

Siemens 3RA2115-0ED15-1AP6 SIRIUS Non-Fused Motor Starter

MPN3RA2115-0ED15-1AP6

Siemens SIRIUS 3RA2115-0ED15-1AP6 non-fused motor starter, direct starter design, size S00, Class 10 thermal overload, coil 187-264 V 50/60 Hz, 690 V rated insulation voltage.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RA2115-0ED15-1AP6 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructiondirect starter
Circuit-breaker sizeS00
Included contactor (type)3RT2015-1AP61
Included circuit-breaker (type)3RV2011-0EA15
Included link module (type)3RA1921-1DA00
3RA2115-0ED15-1AP6 — Ratings & Performance
ParameterValue
Rated motor power at 400 V90 W
Operational current Ie, AC-3 at 400 V0.3 A
Rated voltage at AC-3, max.690 V
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)30 000 000
3RA2115-0ED15-1AP6 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)0.28 ... 0.4 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2
3RA2115-0ED15-1AP6 — Contacts & Control
ParameterValue
Rated value690 V
Rated voltage range at 50 Hz187 ... 242 V
Auxiliary contacts, NO2
Auxiliary contacts, NC1
Auxiliary switch extensionYes
Switching contact typeelectromechanical
3RA2115-0ED15-1AP6 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
Mounting / fastening methodfor snapping onto 60 mm busbar systems
Mounting positionvertical
Width45 mm
Height200 mm
Depth155.1 mm
3RA2115-0ED15-1AP6 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

The Siemens 3RA2115-0ED15-1AP6 is a SIRIUS non-fused motor starter, built as a direct starter in size S00. It integrates a contactor, a thermal bimetallic overload relay, and a magnetic short-circuit trip into one assembly that snaps onto 60 mm busbar systems — a common panel layout for motor control centers. The supplied contactor is 3RT2015-1AP61, the link module is 3RA1921-1DA00, and the circuit-breaker is 3RV2011-0EA15; the busbar adapter 8US1251-5DS10 is also included, so the unit arrives as a ready-to-mount feeder. The coil accepts 187–242 V at 50 Hz and 192–264 V at 60 Hz, covering the common 208–240 V control supply range.

Mounting position is vertical only, per the datasheet. The unit snaps onto 60 mm busbar systems — the standard spacing in Siemens SIRIUS MCCs and many third-party panel layouts. Dimensions are 200 mm high, 45 mm wide, and 155.1 mm deep. Clearance requirements: 20 mm upward, 10 mm downward, 9 mm at the side, zero forward or backward. That 45 mm width is a single 45 mm module, so it occupies one slot in a typical busbar grid. Wire sizing for main contacts: stranded 0.5–4 mm², or 2×(0.75–2.5 mm²). AWG equivalents are 2×(20–16), with a note that only the contactor side accepts 2×(18–14) and 2×12. The product extension for an auxiliary switch is available, so you can add a feedback contact for PLC status monitoring without modifying the main assembly.

Environmental and Duty Ratings

Operating temperature range is –20 to +60 °C; storage is –50 to +80 °C; transport range is –55 to +80 °C. Type of assignment is 2, which means Type 2 coordination: under a short-circuit fault, the starter remains operational after clearing the fault — no replacement of the contactor or overload relay required. That is a key specification for production lines where downtime for component swap is unacceptable.

Frequently asked questions

What is the rated current range of 3RA2115-0ED15-1AP6?

The evidence does not list a specific rated current range for this order code. The overload relay is thermal bimetallic and Class 10; the circuit-breaker supplied is 3RV2011-0EA15. For the exact setting range, refer to the datasheet for that breaker.

MPN
3RA2115-0ED15-1AP6