Motor power and trip class
The 3RA2115-0HA15-1AP6: Rated motor power is 180 W at 400 V, 250 W at 500 V, and 370 W at 690 V — these are AC-3 switching values for standard three-phase induction motors. The short-circuit trip is magnetic (instantaneous), and the unit includes a supplied circuit-breaker (3RV2011-0HA15) and contactor (3RT2015-1AP61) integrated via a link module (3RA1921-1DA00). This is a direct starter — no reversing or star-delta — for simple on/off motor control. Surge voltage withstand is 6 kV, and the operating frequency is 50/60 Hz. Coil voltage is 187–242 V at 50 Hz and 192–264 V at 60 Hz — a wide-range coil that covers 200–240 VAC supplies without a tap change.
Mounting and panel fit
Snap-mounts onto 35 mm DIN rail or screws in place with an additional push-in lug. Mounting position is vertical. Dimensions: 45 mm wide, 97.1 mm deep, 167.2 mm high — size S00 footprint. Clearance needed: 20 mm upward, 10 mm downward, 9 mm at the sides, 0 mm forward or backward. Operating temperature range is -20 to +60 °C; storage range is -50 to +80 °C. Pollution degree 3 (industrial environment with conductive or dry non-conductive pollution).