Skip to main content
Siemens 3RA2115-1CA15-1AP6 — Motor Starters

Siemens 3RA2115-1CA15-1AP6 SIRIUS Motor Starter, 750 W

MPN3RA2115-1CA15-1AP6

Siemens SIRIUS 3RA2115-1CA15-1AP6 non-fused motor starter, direct starter design, Size S00, 750 W at 400 V, Class 10, 45 mm width, snap-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RA2115-1CA15-1AP6 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructiondirect starter
Circuit-breaker sizeS00
Included contactor (type)3RT2015-1AP61
Included circuit-breaker (type)3RV2011-1CA15
Included link module (type)3RA1921-1DA00
3RA2115-1CA15-1AP6 — Ratings & Performance
ParameterValue
Rated motor power at 400 V750 W
Operational current Ie, AC-3 at 400 V1.9 A
Rated voltage at AC-3, max.690 V
Rated motor power at 460/480 V (hp)1 hp
Rated motor power at 575/600 V (hp)1.5 hp
Rated current at 480 V2.15 A
Rated current at 600 V2.24 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)30 000 000
3RA2115-1CA15-1AP6 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)1.8 ... 2.5 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2
3RA2115-1CA15-1AP6 — Contacts & Control
ParameterValue
Rated value690 V
Rated voltage range at 50 Hz187 ... 242 V
Auxiliary contacts, NO2
Auxiliary contacts, NC1
Auxiliary switch extensionYes
Switching contact typeelectromechanical
3RA2115-1CA15-1AP6 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
Mounting / fastening methodSnap-mounted to DIN rail or screw-mounted with additional push-in lug
Mounting positionvertical
Width45 mm
Height167.2 mm
Depth97.1 mm
3RA2115-1CA15-1AP6 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

S00 frame, 45 mm wide — what fits in the panel

The 3RA2115-1CA15-1AP6: It snaps onto the DIN rail or can be screw-mounted with an additional push-in lug, and the mounting position is vertical with specified clearance: 20 mm upward, 10 mm downward, and 9 mm at the side.

Class 10 trip and the thermal bimetal release

Rated power is 750 W at 400 V (50 Hz), with a voltage range of 187–242 V at 50 Hz and 192–264 V at 60 Hz, so it covers common European and North American control voltages without a separate transformer.

Supplied as a complete assembly — contactor and link module included

The starter ships with the 3RT2015-1AP61 contactor and the 3RA1921-1DA00 link module already matched, so there is no separate sizing or wiring of the contactor coil to the overload — it arrives as a direct starter assembly.

Frequently asked questions

Where can I buy 3RA2115-1CA15-1AP6 and get a price?

Submit a request for quote to confirm availability and current pricing for your quantity.

MPN
3RA2115-1CA15-1AP6