What fits in the panel — S00 footprint and mounting
The 3RA2115-1DA15-1AP6: Its 45 mm width and 167.2 mm height leave room for adjacent feeders in a multi-motor control panel; the 97.1 mm depth keeps it clear of the gland plate on a 120 mm-deep enclosure backplate. Mounting position is vertical only. Clearance requirements: 20 mm above, 10 mm below, and 9 mm at the sides — no extra space needed forward or backward.
Motor protection — Class 10 and thermal bimetallic release
That is fast enough to protect a standard squirrel-cage motor during a stalled-rotor start without nuisance tripping on a normal acceleration profile. Rated for AC-3 switching duty up to 690 V maximum. The supplied contactor is a 3RT2015-1AP61; the link module is 3RA1921-1DA00.
Motor power ratings across common voltages
At 230 V it handles 0.75 hp; at 200/208 V, 0.5 hp. The coil accepts 187–242 V at 50 Hz or 192–264 V at 60 Hz.
Environmental limits and pollution degree
Operates from -20 to +60 °C; stores from -50 to +80 °C; survives transport from -55 to +80 °C. Pollution degree 3 means it is rated for the conductive-dust and condensation environment typical of an industrial control panel without a sealed enclosure.