Skip to main content
Siemens 3RA2115-1EA15-1AK6 — Motor Starters

Siemens 3RA2115-1EA15-1AK6 SIRIUS Motor Starter

MPN3RA2115-1EA15-1AK6

Siemens SIRIUS 3RA2115-1EA15-1AK6 non-fused motor starter, size S00, direct starter, Class 10 thermal bimetallic overload, 2 hp at 460/480 V, 45 mm width, snap-on DIN rail.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA2115-1EA15-1AK6 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructiondirect starter
Circuit-breaker sizeS00
Included contactor (type)3RT2015-1AK61
Included circuit-breaker (type)3RV2011-1EA15
Included link module (type)3RA1921-1DA00

Ratings & Performance

3RA2115-1EA15-1AK6 — Ratings & Performance
ParameterValue
Rated motor power at 400 V1 500 W
Operational current Ie, AC-3 at 400 V3.6 A
Rated voltage at AC-3, max.690 V
Rated motor power at 460/480 V (hp)2 hp
Rated motor power at 575/600 V (hp)3 hp
Rated current at 480 V3.95 A
Rated current at 600 V4 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)30 000 000

Protection & Tripping

3RA2115-1EA15-1AK6 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)2.8 ... 4 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2

Contacts & Control

3RA2115-1EA15-1AK6 — Contacts & Control
ParameterValue
Rated value690 V
Rated voltage range at 50 Hz93.5 ... 121 V
Auxiliary contacts, NO2
Auxiliary contacts, NC1
Auxiliary switch extensionYes
Switching contact typeelectromechanical

Mechanical & Connection

3RA2115-1EA15-1AK6 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
Mounting / fastening methodSnap-mounted to DIN rail or screw-mounted with additional push-in lug
Mounting positionvertical
Width45 mm
Height167.2 mm
Depth97.1 mm

Environmental

3RA2115-1EA15-1AK6 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

What this SIRIUS motor starter covers

The 3RA2115-1EA15-1AK6 is a non-fused direct starter from the Siemens SIRIUS range, size S00, combining a 3RT2015-1AK61 contactor with a thermal bimetallic overload relay in a single 45 mm-wide package. It is rated for motor loads up to 2 hp at 460/480 V (AC-3) and delivers 3.95 A at 480 V, with a Class 10 trip curve that clears overloads before the motor windings overheat under locked-rotor conditions.

Mounting and panel fit

Dimensions are 167.2 mm high by 45 mm wide by 97.1 mm deep — it fits standard S00 feeder slots without protruding beyond the panel depth envelope.

Coil voltage and wiring

The coil accepts 93.5–121 V at 50 Hz and 96–132 V at 60 Hz, covering common 110/120 V control circuits without a separate transformer tap.

Frequently asked questions

What is the 3RA2115-1EA15-1AK6 rated for at 460/480 V?

It is rated 2 hp at 460/480 V, drawing 3.95 A at 480 V in AC-3 duty — suitable for typical three-phase motor loads in that power band.

Can I order the 3RA2115-1EA15-1AK6 here?

Yes. Submit an RFQ for current pricing and availability.

MPN
3RA2115-1EA15-1AK6