Skip to main content
Siemens 3RA2115-4AA18-1BB4 — Motor Starters

Siemens 3RA2115-4AA18-1BB4 SIRIUS Motor Starter

MPN3RA2115-4AA18-1BB4

Siemens SIRIUS 3RA2115-4AA18-1BB4 non-fused motor starter, size S00, direct starter, AC-3 rated 14 A at 480 V, Class 10 thermal overload, 24 V coil, snap-on DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RA2115-4AA18-1BB4 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructiondirect starter
Circuit-breaker sizeS00
Included contactor (type)3RT2018-1BB41
Included circuit-breaker (type)3RV2011-4AA15
Included link module (type)3RA1921-1DA00
3RA2115-4AA18-1BB4 — Ratings & Performance
ParameterValue
Rated motor power at 400 V7 500 W
Operational current Ie, AC-3 at 400 V15.5 A
Rated voltage at AC-3, max.690 V
Rated motor power at 460/480 V (hp)10 hp
Rated motor power at 575/600 V (hp)10 hp
Rated current at 480 V14 A
Rated current at 600 V11 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)30 000 000
3RA2115-4AA18-1BB4 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)11 ... 16 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)1
3RA2115-4AA18-1BB4 — Contacts & Control
ParameterValue
Rated value24 V
Auxiliary contacts, NO2
Auxiliary contacts, NC1
Auxiliary switch extensionYes
Switching contact typeelectromechanical
3RA2115-4AA18-1BB4 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
Mounting / fastening methodSnap-mounted to DIN rail or screw-mounted with additional push-in lug
Mounting positionvertical
Width45 mm
Height167.2 mm
Depth97.1 mm
3RA2115-4AA18-1BB4 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

Panel fit and mounting — S00 form factor

The 3RA2115-4AA18-1BB4 is a size S00 direct starter, 45 mm wide by 167.2 mm tall by 97.1 mm deep — it occupies one standard 45 mm DIN-rail slot with snap-on mounting, or can be screw-mounted using the push-in lug. Mounting position is vertical only; the specified clearance above the unit is 20 mm, with 10 mm below and 9 mm at the side. No forward or backward clearance is needed, so the unit can sit flush against a panel backplane.

Motor starting duty — AC-3 ratings and trip class

At 400 V the power rating is 7.5 kW. The supplied contactor is a 3RT2018-1BB41, and the link module is 3RA1921-1DA00 — these are the matched components that make up the assembled starter, so the coordination between contactor and overload is factory-set.

Wiring and termination

The coil is rated 24 V, 50/60 Hz, matching standard control voltages in industrial panels.

MPN
3RA2115-4AA18-1BB4