Skip to main content
Siemens 3RA2120-0JA23-0BB4 — Motor Starters

Siemens 3RA2120-0JA23-0BB4 SIRIUS non-fused motor starter

MPN3RA2120-0JA23-0BB4

Siemens SIRIUS 3RA2120-0JA23-0BB4 non-fused motor starter, direct starter design, size S0, 24 V DC coil, Class 10 thermal overload, 690 V AC-3 max, 50-60 Hz.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RA2120-0JA23-0BB4 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS0
Product design / constructiondirect starter
Circuit-breaker sizeS00
Included contactor (type)3RT2023-1BB40
Included circuit-breaker (type)3RV2011-0JA10
Included link module (type)3RA2921-1BA00
3RA2120-0JA23-0BB4 — Ratings & Performance
ParameterValue
Rated motor power at 400 V250 W
Operational current Ie, AC-3 at 400 V0.85 A
Rated voltage at AC-3, max.690 V
Rated motor power at 575/600 V (hp)0.5 hp
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)10 000 000
3RA2120-0JA23-0BB4 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)0.7 ... 1 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2
3RA2120-0JA23-0BB4 — Contacts & Control
ParameterValue
Rated value24 V
Auxiliary contacts, NO1
Auxiliary contacts, NC1
Auxiliary switch extensionYes
Switching contact typeelectromechanical
3RA2120-0JA23-0BB4 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (16 ... 12), 2x (14 ... 8)
Mounting / fastening methodSnap-mounted to DIN rail or screw-mounted with additional push-in lug
Mounting positionvertical
Width45 mm
Height193.1 mm
Depth107 mm
3RA2120-0JA23-0BB4 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

The 3RA2120-0JA23-0BB4: This is a SIRIUS non-fused motor starter, direct starter design, size S0. It combines a contactor and a thermal overload relay in one unit, intended for switching and protecting three-phase motors up to 690 V AC-3. The 24 V DC coil draws 5.9 W holding power — a common control voltage for PLC-driven panels. The coil is electromechanical, so expect a distinct pick-up and drop-out threshold; verify your DC supply can deliver the inrush (not listed here) before committing the BOM. Motor power ratings are given per voltage: 250 W at 400 V, 370 W at 500 V, 550 W at 690 V, and 0.5 hp at 575/600 V. These are the maximum full-load motor sizes the starter can handle at those line voltages — oversizing the motor beyond these figures risks nuisance tripping or contact welding under locked-rotor current.

The mounting position is vertical only — horizontal mounting would change the thermal overload calibration. Clearance requirements: 30 mm upward, 10 mm forward, 10 mm downward, 9 mm at the side, and 0 mm backward (flush to the panel backplane). These are the minimum free-air gaps for heat dissipation and arc flash clearance. Dimensions: 193.1 mm high, 45 mm wide, 107 mm deep. The 45 mm width (about 2.5 modular DIN units) fits standard enclosure cutouts. The supplied circuit-breaker is a 3RV2011-0JA10 (size S00), and the supplied contactor is a 3RT2023-1BB40 — these are matched by the factory for coordination, so swapping either component breaks the short-circuit rating.

Environmental and compliance notes

Operating temperature range is -20 to +60 °C; storage range is -50 to +80 °C; transport range is -55 to +80 °C. The degree of pollution is 3 (conductive pollution or dry non-conductive pollution that becomes conductive due to condensation — typical in industrial control panels without climate control). The substance prohibition date is 03/01/2017, indicating RoHS compliance per EU Directive 2011/65/EU.

MPN