Skip to main content
Siemens 3RA2120-1GA24-0AP6 — Motor Starters

Siemens 3RA2120-1GA24-0AP6 SIRIUS Motor Starter, Class 10

MPN3RA2120-1GA24-0AP6

Siemens SIRIUS 3RA2120-1GA24-0AP6 non-fused direct motor starter, Size S0, Class 10 thermal overload, 690 V AC-3, 45 mm width, snap-on DIN rail.

StockIn Stock (28)
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026Stock-verified to date
How we verify every order →

Specifications

Identification

3RA2120-1GA24-0AP6 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS0
Product design / constructiondirect starter
Circuit-breaker sizeS00
Included contactor (type)3RT2024-1AP60
Included circuit-breaker (type)3RV2011-1GA10
Included link module (type)3RA2921-1AA00

Ratings & Performance

3RA2120-1GA24-0AP6 — Ratings & Performance
ParameterValue
Rated motor power at 400 V2 200 W
Operational current Ie, AC-3 at 400 V5 A
Rated voltage at AC-3, max.690 V
Rated motor power at 460/480 V (hp)3 hp
Rated motor power at 575/600 V (hp)5 hp
Rated current at 480 V4.8 A
Rated current at 600 V6.3 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V

Protection & Tripping

3RA2120-1GA24-0AP6 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)4.5 ... 6.3 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2

Contacts & Control

3RA2120-1GA24-0AP6 — Contacts & Control
ParameterValue
Rated value690 V
Rated voltage range at 50 Hz176 ... 242 V
Auxiliary contacts, NO1
Auxiliary contacts, NC1
Auxiliary switch extensionYes
Switching contact typeelectromechanical

Mechanical & Connection

3RA2120-1GA24-0AP6 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Mounting / fastening methodSnap-mounted to DIN rail or screw-mounted with additional push-in lug
Mounting positionvertical
Width45 mm
Height193.1 mm
Depth97.1 mm

Environmental

3RA2120-1GA24-0AP6 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

Integrated motor starting for S0 load feeders

The 3RA2120-1GA24-0AP6 is a SIRIUS non-fused direct starter combining a 3RT2024-1AP60 contactor and a thermal bimetallic overload relay in a single S0-size package, pre-assembled with the 3RA2921-1AA00 link module.

Mounting and panel integration

Vertical mounting position only; clearance requirements are 30 mm upwards, 10 mm forwards, 10 mm downwards, 9 mm at the side, and 0 mm backwards — plan the enclosure depth and gland plate accordingly.

Thermal and environmental limits

Operates from -20 to +60 °C with pollution degree 3 (conductive or dry non-conductive pollution becoming conductive) — suitable for industrial control panels without climate control, though the thermal overload setting must be adjusted for ambient temperature above 40 °C per the derating curve. Storage range -50 to +80 °C and transport range -55 to +80 °C cover cold warehouses and unheated freight.

Frequently asked questions

What are the key ratings for 3RA2120-1GA24-0AP6?

AC-3 rated voltage 690 V maximum, Class 10 thermal overload, S0 size.

What clearance is needed around 3RA2120-1GA24-0AP6 in a panel?

30 mm upwards, 10 mm forwards, 10 mm downwards, 9 mm at the side, and 0 mm backwards. The starter must be mounted vertically.

MPN
3RA2120-1GA24-0AP6