Integrated motor starting for S0 load feeders
The 3RA2120-1GA24-0AP6 is a SIRIUS non-fused direct starter combining a 3RT2024-1AP60 contactor and a thermal bimetallic overload relay in a single S0-size package, pre-assembled with the 3RA2921-1AA00 link module.
Mounting and panel integration
Vertical mounting position only; clearance requirements are 30 mm upwards, 10 mm forwards, 10 mm downwards, 9 mm at the side, and 0 mm backwards — plan the enclosure depth and gland plate accordingly.
Thermal and environmental limits
Operates from -20 to +60 °C with pollution degree 3 (conductive or dry non-conductive pollution becoming conductive) — suitable for industrial control panels without climate control, though the thermal overload setting must be adjusted for ambient temperature above 40 °C per the derating curve. Storage range -50 to +80 °C and transport range -55 to +80 °C cover cold warehouses and unheated freight.