Active production — what that means for your BOM line
The 3RA2125-4AA26-0AP6: The part ships as a factory-assembled unit: a 3RT2026-1AP60 contactor paired with a 3RA2921-1AA00 link module and a thermal bimetallic overload relay, all in one S0-size package.
Motor ratings across supply voltages
At 575/600 V the output is 12.2 A and 10 hp. For 230 V single-phase or low-line three-phase applications: 2 hp at 230 V, 5 hp at 220/230 V. At 200/208 V it delivers 3 hp. The control coil accepts 176–242 V at 50 Hz and 192–264 V at 60 Hz — covers the common 208–240 V control transformer taps without a separate coil change.
Trip class and overload protection
The bimetallic overload release is ambient-compensated across the -20 to +60 °C operating range, so the trip point stays stable whether the panel sits in a conditioned room or a hot enclosure.
Panel fit and mounting
Snap-mounts onto 35 mm DIN rail or screw-mounts with an additional push-in lug. The 45 mm width and 97.1 mm depth fit standard S0 feeder spacing — three units side-by-side occupy 135 mm of rail. Mounting position is vertical. Clearance requirements: 30 mm upwards, 10 mm forwards, 10 mm downwards, 9 mm at the side, zero backwards. Wire range for main contacts: 1–10 mm² stranded, or 2× (2.5–6 mm²) — covers most motor feeder cables up to 10 AWG.