S0 frame, CLASS 10 trip — what that means for the panel
The 3RA2125-4BD26-0AK6: This is a Siemens SIRIUS 3RA2 non-fused direct motor starter, size S0, that ships as a pre-assembled unit: the supplied contactor (3RT2026-1AK60) and link module (3RA2921-1AA00) are matched to the thermal bimetallic overload relay.
Busbar snap-on and enclosure fit
Mounts by snapping directly onto 60 mm busbar systems — no separate DIN rail adapter needed for the main power feed. The S0 footprint is 45 mm wide, 260 mm tall, 155 mm deep. Clearance requirements: 30 mm upward, 10 mm forward, 10 mm downward, 9 mm at the sides, and zero backward — so you can push it against the back panel.