36 A AC-3 direct starter — what it handles
The 3RA2130-4PA35-0AP0: Trip Class 10 means it clears a stall or locked-rotor condition within 10 seconds at the cold-state calibration point — standard for general-purpose motor protection on pumps, fans, and conveyors where the starting time stays under a few seconds.
Panel fit and mounting
Mounts on two 35 mm DIN rails via screw and snap-on fastening; the 55 mm width and 150 mm depth fit a standard S2 feeder footprint. Vertical or horizontal orientation is allowed, with 50 mm clearance upward and 32 mm forward for wiring access — no tight squeeze on the screw terminals. The supplied contactor is a 3RT2035-1AP00, paired with a 3RA2931-1AA00 link module — the assembly arrives as a single order code, saving the BOM line for the contactor and thermal overload separately.
Environmental limits
Runs from -20 °C to +60 °C during operation, with storage and transport range from -50 °C to +80 °C. The temperature compensation is active across the same -20 to +60 °C band, so the trip curve stays within spec in a warm enclosure.