Skip to main content
Siemens 3RA2140-4KB46-0NB3 — Motor Starters

Siemens 3RA2140-4KB46-0NB3 SIRIUS Motor Starter

MPN3RA2140-4KB46-0NB3

Siemens SIRIUS 3RA2140-4KB46-0NB3 non-fused motor starter, S3 size, 75 A at 480 V, Class 10, direct starter, 3RT2 contactor, snap-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RA2140-4KB46-0NB3 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS3
Product design / constructiondirect starter
Circuit-breaker sizeS3
Included contactor (type)3RT2140-460NB3
Included circuit-breaker (type)3RV2041-4KA10
Included link module (type)3RA2942-1AA00
3RA2140-4KB46-0NB3 — Ratings & Performance
ParameterValue
Rated motor power at 400 V37 kW
Operational current Ie, AC-3 at 400 V75 A
Rated voltage at AC-3, max.690 V
Rated motor power at 460/480 V (hp)75 hp
Rated motor power at 575/600 V (hp)75 hp
Rated current at 480 V75 A
Rated current at 600 V75 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)10 000 000
3RA2140-4KB46-0NB3 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)65 000 A
Overload release setting range (current)57 ... 75 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2
3RA2140-4KB46-0NB3 — Contacts & Control
ParameterValue
Rated value20 ... 33 V
Rated voltage range at 50 Hz20 ... 33 V
Auxiliary contacts, NO1
Auxiliary contacts, NC1
Auxiliary switch extensionYes
Switching contact typeelectromechanical
3RA2140-4KB46-0NB3 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (10 ... 1/0), 1x (10 ... 2)
Mounting / fastening methodSnap-mounted to DIN rail or screw-mounted with additional push-in lug
Mounting positionvertical
Width70 mm
Height332 mm
Depth200 mm
3RA2140-4KB46-0NB3 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6.7g / 5 ms

Product details

Motor ratings and trip class

The 3RA2140-4KB46-0NB3: At 400 V it delivers 37 kW.

Mounting and panel fit

Snap-mounts onto DIN rail or screws onto a backplate with the included push-in lug. Mounting position is vertical only. Dimensions are 332 mm high, 70 mm wide, 200 mm deep. Clearance: 50 mm above, 32 mm in front, 10 mm below, 10 mm at the sides, zero behind.

Supplied components and wiring

The starter ships with a 3RT2140-460NB3 contactor and a 3RA2942-1AA00 link module. The overload release is thermal bimetallic, electromechanical switching. Main contact wire range: stranded 10–70 mm², or two conductors 2.5–50 mm² each. Pollution degree 3, suitable for industrial environments with conductive dust or moisture.

Operating conditions and lifecycle

Rated for ambient operation -20 to +60 °C; storage -50 to +80 °C; transport -55 to +80 °C.

Frequently asked questions

What is the maximum motor power this starter handles at 480 V?

At 480 V it is rated 75 A, which corresponds to 75 hp. At 400 V it delivers 37 kW.

What clearance is needed around this starter in the panel?

Allow 50 mm above, 32 mm in front, 10 mm below, and 10 mm at the sides. Zero clearance behind the unit.

MPN
3RA2140-4KB46-0NB3