Skip to main content
Siemens 3RA2210-0CA15-2AP6 — Motor Starters

Siemens 3RA2210-0CA15-2AP6 SIRIUS Reversing Motor Starter

MPN3RA2210-0CA15-2AP6

Siemens SIRIUS 3RA2210-0CA15-2AP6 non-fused reversing motor starter, size S00, Class 10 thermal bimetallic overload, 690 V AC-3, 50-60 Hz, snap-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RA2210-0CA15-2AP6 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructionreversing starter
Circuit-breaker sizeS00
Included contactor (type)3RT2015-1AP62
Included circuit-breaker (type)3RV2011-0CA10
Included link module (type)3RA1921-1DA00
3RA2210-0CA15-2AP6 — Ratings & Performance
ParameterValue
Rated motor power at 400 V60 W
Operational current Ie, AC-3 at 400 V0.2 A
Rated voltage at AC-3, max.690 V
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)30 000 000
3RA2210-0CA15-2AP6 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)0.18 ... 0.25 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2
3RA2210-0CA15-2AP6 — Contacts & Control
ParameterValue
Rated value690 V
Rated voltage range at 50 Hz187 ... 242 V
Auxiliary contacts, NO0
Auxiliary contacts, NC1
Auxiliary switch extensionYes
Switching contact typeelectromechanical
3RA2210-0CA15-2AP6 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
Mounting / fastening methodSnap-mounted to DIN rail or screw-mounted with additional push-in lug
Mounting positionvertical
Width90 mm
Height170 mm
Depth97.1 mm
3RA2210-0CA15-2AP6 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

SIRIUS S00 reversing starter — what's in the box

The 3RA2210-0CA15-2AP6: This is a fully assembled non-fused reversing motor starter from the SIRIUS family, size S00. It ships with the 3RT2015-1AP62 contactor, the 3RV2011-0CA10 circuit-breaker, and the 3RA1921-1DA00 link module already integrated — one order code, one assembly, no separate sourcing of sub-components. That's the standard protection for standard-duty squirrel-cage motors — not for high-inertia loads that need Class 20 or longer. Rated insulation voltage is 690 V, and the maximum AC-3 switching voltage is also 690 V, so it covers 400 V, 480 V, and 575 V motor feeders without derating. The operating frequency is 50-60 Hz, which is the global norm for industrial mains.

Panel fit — S00 frame dimensions and clearances

The starter measures 170 mm high, 90 mm wide, and 97.1 mm deep. That's the standard S00 footprint — it shares the same mounting hole pattern and DIN-rail clip as other S00 SIRIUS devices, so swapping in a different S00 starter or contactor doesn't require re-drilling the backplate. Clearance requirements: 20 mm upwards, 10 mm downwards, 9 mm at the sides, and zero forwards or backwards. That 9 mm side gap is tight — adjacent devices with side-mounted aux blocks may need more. AWG equivalents are 2x (20-16) for the contactor, and 2x (18-14) or 2x 12 for the circuit-breaker side. The terminal design accepts ferruled stranded or solid conductors — no special crimp tool needed beyond standard ferrule dies.

Lifecycle and sourcing — current production, no cross-reference needed

Compliance: RoHS substance prohibition date is 03/01/2017, which covers the EU RoHS 2 (2011/65/EU) and the updated RoHS 3 (2015/863) scope. The starter carries the CE mark and is designed to IEC/EN 60947-4-1 for motor starters and IEC/EN 60947-2 for the integrated circuit-breaker.

Frequently asked questions

What is the Trip Class of this motor starter?

This is the standard protection for general-purpose squirrel-cage motors under normal starting duty.

What are the mounting clearances for the 3RA2210-0CA15-2AP6?

Minimum clearances: 20 mm above, 10 mm below, 9 mm at the sides, and zero forwards or backwards. Mounting position is vertical only, on a 35 mm DIN rail or with screw-mount using the push-in lug.

What compliance documentation does Siemens provide for this starter?

The RoHS substance prohibition date is 03/01/2017, covering EU RoHS 2 and RoHS 3. The starter is designed to IEC/EN 60947-4-1 (motor starters) and IEC/EN 60947-2 (circuit-breaker), and carries CE marking.

MPN
3RA2210-0CA15-2AP6