Reversing starter for 60 mm busbar systems
The 3RA2210-0ED15-2AP0: It ships as a pre-assembled unit containing the 3RT2015-1AP02 contactor and the 3RA1921-1DA00 link module, so the reversing interlock is factory-set and the wiring between the two contactors is internal.
Trip Class 10 and thermal coordination
This coordinates with standard motor starting profiles — a pump or fan that accelerates within 5–8 seconds stays under the curve, while a stalled rotor condition clears fast enough to protect the winding insulation. The operating temperature range is -20 to +60 °C, with the same range for temperature compensation — the thermal model adjusts the trip threshold as the ambient in the panel rises, so you don't get nuisance trips on a hot afternoon or fail to protect on a cold startup.
Mounting dimensions and clearance
The unit measures 155 mm deep, 90 mm wide, and 204 mm tall. Mounting is vertical only, and the clearance requirements are specific: 50 mm upwards, 32 mm forwards, 10 mm downwards, 10 mm at the side, and 0 mm backwards — the back face sits flush against the busbar system. The main circuit uses screw-type terminals, which is the standard for panel builders who prefer a torque-controlled connection over spring-cage for high-current reversing circuits. The S00 frame size keeps the footprint compact enough for a 600 mm wide panel to carry multiple reversing starters side by side.