Skip to main content
Siemens 3RA2210-0EH15-2BB4 — Motor Starters

Siemens 3RA2210-0EH15-2BB4 SIRIUS Reversing Starter

MPN3RA2210-0EH15-2BB4
Active

Siemens SIRIUS reversing starter, Size S00, 0.4 A at 400 V AC-3, Class 10, spring-loaded terminals, for 60 mm busbar systems.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA2210-0EH15-2BB4 — Identification
ParameterValue
Product designationReversing starter
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructionfor 60 mm busbars
Circuit-breaker sizeS00
Included contactor (type)3RT2015-2BB42
Included circuit-breaker (type)3RV2011-0EA20
Included link module (type)3RA2911-2AA00

Ratings & Performance

3RA2210-0EH15-2BB4 — Ratings & Performance
ParameterValue
Rated motor power at 400 V90 kW
Rated voltage at AC-3, max.690 V
Rated current at 480 V0.4 A
Rated current at 600 V0.4 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V

Protection & Tripping

3RA2210-0EH15-2BB4 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)150 000 A
Overload release setting range (current)0.28 ... 0.4 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2

Contacts & Control

3RA2210-0EH15-2BB4 — Contacts & Control
ParameterValue
Rated value24 ... 24 V
Control supply voltage typeDC
Auxiliary switch extensionYes
Switching contact typeelectromechanical

Communication

3RA2210-0EH15-2BB4 — Communication
ParameterValue
AS-Interface protocol supportNo

Mechanical & Connection

3RA2210-0EH15-2BB4 — Mechanical & Connection
ParameterValue
Mounting / fastening methodfor snapping onto 60 mm busbar systems
Mounting positionvertical
Width90 mm
Height260 mm
Depth155 mm

Environmental

3RA2210-0EH15-2BB4 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-50 ... +80 °C
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

SIRIUS reversing starter, Size S00 — busbar-mounted motor reversing

The Siemens 3RA2210-0EH15-2BB4 is a SIRIUS reversing starter in Size S00, designed to snap directly onto 60 mm busbar systems — no separate DIN-rail adapter needed for the main power feed. It ships as a factory-assembled unit containing the contactor 3RT2015-2BB42, the link module 3RA2911-2AA00, and the RS assembly kit 3RA2913-1DB2 — one order code covers the reversing pair and the mechanical interlock. The 90 kW rating at 400 V applies to the contactor's motor-switching capacity in this configuration. The thermal bimetallic overload release is set to Trip Class 10 — it protects standard squirrel-cage motors during start-up without nuisance tripping on normal acceleration.

Mounting clearances and panel fit

Dimensions are 155 mm deep, 90 mm wide, 260 mm high. The vertical mounting position is mandatory — the bimetallic trip curve assumes upright orientation for natural convection. Required clearances: 50 mm above, 32 mm in front, 10 mm below, 10 mm at each side, and 0 mm behind (the busbar mount takes the back plane). These gaps must be maintained for arc containment and cooling airflow.

Environmental and compliance documentation

Operating temperature range is -20 to +60 °C; storage and transport range is -50 to +80 °C. The -20 °C floor is common for unheated plant areas — the bimetallic element compensates across the full band. RoHS compliance date is 10 January 2009, covering the EU RoHS recast. The part carries no PROFIsafe or PROFINET IO protocol — it is a hard-wired reversing starter, not a fieldbus slice.

Frequently asked questions

What compliance documentation does Siemens provide for this reversing starter?

RoHS compliance is documented with a substance prohibitance date of 10 January 2009, covering the EU RoHS recast. The unit is a hard-wired electromechanical starter — no fieldbus protocol certificates apply.

What are the key ratings of the 3RA2210-0EH15-2BB4?

The thermal overload release is Trip Class 10. Operating frequency is 50…60 Hz.

MPN
3RA2210-0EH15-2BB4