Reversing starter for 60 mm busbar systems
The 3RA2210-0FS15-2BB4: It ships as a pre-assembled unit with the contactor (3RT2015-2BB42), link module (3RA2911-2AA00), busbar adapter (8US1251-5DS11), RS assembly kit (8US1250-5AS10), and circuit-breaker (3RV2011-0FA20) included.
Rated values and protection design
Rated 120 W at 400 V and 0.5 A at 480 V, with a maximum AC-3 voltage of 690 V. The operating frequency is 50 to 60 Hz, covering standard industrial mains worldwide. Overload protection uses a thermal bimetallic element (CLASS 10), while short-circuit protection is magnetic — both integrated into the supplied circuit-breaker 3RV2011-0FA20. The main circuit terminates via spring-loaded terminals, reducing wiring time compared to screw-clamp alternatives. The unit is rated for vertical mounting only, with a temperature range of -20 to +60 °C during operation and -50 to +80 °C during storage or transport. Clearance requirements: 50 mm upwards, 32 mm forwards, 10 mm downwards, 10 mm at the side, and 0 mm backwards.
Lifecycle and sourcing
The substance prohibitance date of 10/01/2009 indicates RoHS compliance per EU Directive 2002/95/EC.