The 3RA2210-0GH15-2AP0: The unit ships with a 3RT2015-2AP02 contactor and a 3RA2911-2AA00 link module pre-assembled. Terminals are spring-loaded on the main circuit — no screw torque to verify, which speeds panel wiring.
Mounting and panel fit — snaps onto 60 mm busbars
Designed for snapping onto 60 mm busbar systems, not DIN rail. The mounting position is vertical only. Dimensions are 260 mm height × 90 mm width × 155 mm depth — the depth is the critical dimension for enclosure depth clearance. Clearance requirements: 50 mm upwards, 32 mm forwards, 10 mm downwards, 10 mm at the side, 0 mm backwards. These matter for heat dissipation and arc-fault containment in a panel layout. Operating temperature range is -20 to +60 °C; storage and transport range is -50 to +80 °C. The temperature compensation is active across the full operating range, so the overload trip curve stays accurate.