The 3RA2210-0JD15-2BB4: Sourcing is straightforward: we quote this against your BOM quantity through authorized distribution.
AC-3 duty and trip class — what they mean for the motor
The 1 A at 400 V translates to roughly 0.55 kW (0.75 hp) at 400 V three-phase, which is the motor size this S00 frame is built for. The 24 V coil (24... 24 V) is the standard low-voltage control supply for PLC-driven panels.
Mounting on 60 mm busbar systems — panel fit
Designed for snapping onto 60 mm busbar systems (the standard Siemens SIRIUS busbar grid). The mounting position is vertical only. Dimensions: 90 mm wide, 204 mm high, 155 mm deep — the S00 frame size is the smallest in the SIRIUS feeder family, so it fits in tight sub-distribution panels. Clearance requirements: 50 mm upwards, 32 mm forwards, 10 mm downwards, 10 mm at the side, 0 mm backwards. The zero backward clearance means the unit can sit flush against a backplate or busbar support. Operating temperature range is -20 to +60 °C; storage and transport range is -50 to +80 °C.
Compliance and documentation
RoHS compliance date is 10/01/2009 — the starter meets the EU RoHS directive for restricted substances. The SIRIUS series carries CE, UL, CSA, and IEC certifications; the specific approvals for this order code are confirmed in the Siemens certificate database. The supplied contactor (3RT2015-1BB42) is a standard electromechanical unit, not a solid-state or soft-start device.