1.25 A reversing starter, S00 frame, busbar snap-on
The 3RA2210-0KH15-2AP0: It ships as a pre-assembled unit containing the 3RT2015-2AP02 contactor and the 3RA2911-2AA00 link module, so the reversing interlock and mechanical linkage are factory-set — no field assembly of the reversing pair. Mounting is by snapping onto 60 mm busbar systems, not a DIN rail; the vertical mounting position is specified, and the enclosure clearances are 50 mm upward, 32 mm forward, 10 mm downward, and 10 mm at the side.
Trip class and termination — what they mean for the panel
The main current circuit uses spring-loaded terminals (cage-clamp style), so no screw torque verification is needed — solid or ferruled stranded wire is pushed in directly. Operating temperature range is -20 to +60 °C, with storage and transport from -50 to +80 °C — the unit can sit in an unheated warehouse or truck without damage.