Skip to main content
Siemens 3RA2210-1AE15-2BB4 — Motor Starters

Siemens 3RA2210-1AE15-2BB4 Reversing Starter, S00

MPN3RA2210-1AE15-2BB4
Active

Siemens SIRIUS 3RA2210-1AE15-2BB4 reversing starter, size S00, 1.6 A at 400 V AC-3, Class 10, spring-loaded terminals, screw and snap-on mounting on 35 mm DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RA2210-1AE15-2BB4 — Identification
ParameterValue
Product designationReversing starter
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructionfor standard rail or screw mounting
Circuit-breaker sizeS00
Included contactor (type)3RT2015-2BB42
Included circuit-breaker (type)3RV2011-1AA20
Included link module (type)3RA2911-2AA00
3RA2210-1AE15-2BB4 — Ratings & Performance
ParameterValue
Rated motor power at 400 V550 kW
Rated voltage at AC-3, max.690 V
Rated motor power at 460/480 V (hp)1 hp
Rated motor power at 575/600 V (hp)1 hp
Rated current at 480 V1.6 A
Rated current at 600 V1.6 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
3RA2210-1AE15-2BB4 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)150 000 A
Overload release setting range (current)1.1 ... 1.6 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2
3RA2210-1AE15-2BB4 — Contacts & Control
ParameterValue
Rated value24 ... 24 V
Control supply voltage typeDC
Auxiliary switch extensionYes
Switching contact typeelectromechanical
3RA2210-1AE15-2BB4 — Communication
ParameterValue
AS-Interface protocol supportNo
3RA2210-1AE15-2BB4 — Mechanical & Connection
ParameterValue
Mounting / fastening methodscrew and snap-on mounting onto 35 mm DIN rail
Mounting positionvertical
Width90 mm
Height204 mm
Depth97 mm
3RA2210-1AE15-2BB4 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-50 ... +80 °C
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

1.6 A AC-3 at 400 V — what that means on the line

The 3RA2210-1AE15-2BB4: The 1.6 A at 400 V works out to roughly 0.75 kW (1 hp) motor, consistent with the 1 hp rating at 460/480 V and 575/600 V. For a 1.6 A motor, the thermal memory tracks both running and cool-down periods, so a hot restart won't catch you off guard.

Panel fit and mounting — DIN rail or screw, your call

Mounts either by snapping onto 35 mm DIN rail or with screws — the same part covers both, so you don't need a separate adapter for a screw-down panel. The 90 mm width, 204 mm height, and 97 mm depth fit a standard S00 footprint; plan for 50 mm clearance above, 32 mm in front, and 10 mm on the sides and below for airflow and wiring access. The supplied contactor is a 3RT2015-2BB42 and the link module is a 3RA2911-2AA00, so the reversing interlock is built into the assembly, not something you wire up from scratch.

Active production — no lifecycle surprises

That means you can spec it into a new BOM without worrying about a last-time-buy window closing mid-project. The 24 V DC coil voltage is common across the SIRIUS family, so panel spares can be shared with other S00 contactors in the same cabinet. RoHS compliance date of October 1, 2009 is on file — the part meets the EU substance restrictions.

Frequently asked questions

What is the 1.6 A rating at 400 V — is that the full-load motor current or the contact rating?

The maximum operating voltage is 690 V AC-3 and AC-3e. For a 1.6 A motor at 400 V, you're looking at roughly 0.75 kW (1 hp).

What clearance do I need around this reversing starter in the panel?

The mounting position is vertical. Allow 50 mm upwards, 32 mm forwards, 10 mm downwards, and 10 mm at the sides for airflow and wiring access. Backwards clearance is 0 mm — it can sit flush against the back panel or mounting plate.

MPN