Skip to main content
Siemens 3RA2210-1CD15-2AP6 — Motor Starters

Siemens 3RA2210-1CD15-2AP6 SIRIUS Reversing Starter

MPN3RA2210-1CD15-2AP6

Siemens SIRIUS 3RA2210-1CD15-2AP6 reversing motor starter, Size S00, non-fused, Class 10, 690 V, thermal bimetallic overload, supplied with contactor 3RT2015-1AP62 and link module 3RA1921-1DA00.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA2210-1CD15-2AP6 — Identification
ParameterValue
Product designationnon-fused motor starter 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructionreversing starter
Circuit-breaker sizeS00
Included contactor (type)3RT2015-1AP62
Included circuit-breaker (type)3RV2011-1CA10
Included link module (type)3RA1921-1DA00

Ratings & Performance

3RA2210-1CD15-2AP6 — Ratings & Performance
ParameterValue
Rated motor power at 400 V750 W
Operational current Ie, AC-3 at 400 V1.9 A
Rated voltage at AC-3, max.690 V
Rated motor power at 460/480 V (hp)1 hp
Rated motor power at 575/600 V (hp)1.5 hp
Rated current at 480 V2.15 A
Rated current at 600 V2.24 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)30 000 000

Protection & Tripping

3RA2210-1CD15-2AP6 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)1.8 ... 2.5 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2

Contacts & Control

3RA2210-1CD15-2AP6 — Contacts & Control
ParameterValue
Rated value690 V
Rated voltage range at 50 Hz187 ... 242 V
Auxiliary contacts, NO0
Auxiliary contacts, NC1
Auxiliary switch extensionYes
Switching contact typeelectromechanical

Mechanical & Connection

3RA2210-1CD15-2AP6 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
Mounting / fastening methodfor snapping onto 60 mm busbar systems
Mounting positionvertical
Width90 mm
Height200 mm
Depth155.1 mm

Environmental

3RA2210-1CD15-2AP6 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-55 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

Reversing starter — what it does that a contactor pair alone cannot

The 3RA2210-1CD15-2AP6: This is a factory-assembled reversing starter, not a field-built contactor pair with mechanical interlock. The supplied contactor 3RT2015-1AP62 and link module 3RA1921-1DA00 are matched at the factory — the interlock timing and the reversing logic are tested as a unit, which saves panel build time and eliminates wiring errors on a reversing circuit. Rated for AC-3 switching up to 690 V, with a thermal bimetallic overload release (Class 10) that protects the motor against sustained overcurrent without nuisance tripping on normal starting inrush.

Mounting and panel fit — busbar snap-on, not DIN rail

The fastening method is for snapping onto 60 mm busbar systems — not a standard DIN rail. This means the panel backplate must have the busbar profile, or you need an adapter. Mounting position is vertical only. Dimensions: 200 mm height, 90 mm width, 155.1 mm depth. Clearance: 20 mm upwards, 10 mm downwards, 9 mm at the side, zero forwards or backwards.