Reversing starter, S00 frame, active production
The 3RA2210-1DA15-2AP0: This unit ships as a complete assembly: a 3RT2015-1AP02 contactor paired with a 3RA1921-1DA00 link module, ready for screw or snap-on mounting onto 35 mm DIN rail.
Panel fit and mounting constraints
Dimensions are 170 mm high, 90 mm wide, 97 mm deep — the S00 footprint fits standard motor-starter slots in most IEC panels. Mounting position is vertical only. Clearance requirements: 50 mm above, 32 mm in front, 10 mm below, 10 mm at the sides, and zero behind the unit. The backwards clearance of 0 mm means it sits flush against the backplane or DIN rail. Main circuit connections use screw-type terminals — standard for panel wiring, no special tooling needed.
Duty ratings and thermal limits
Rated operational voltage is 690 V, covering 400 V and 480 V systems common in North American and European plants. Horsepower ratings span from 0.12 hp at 110/120 V up to 3 hp at 575/600 V. Operating temperature range is -20 to +60 °C, with storage and transport limits from -50 to +80 °C. The temperature compensation is active across the full operating range.