Skip to main content
Siemens 3RA2210-1ED15-2AK6 — Motor Starters

Siemens 3RA2210-1ED15-2AK6 SIRIUS Non-Fused Reversing

MPN3RA2210-1ED15-2AK6

Siemens SIRIUS 3RA2210-1ED15-2AK6 non-fused reversing starter, Size S00, Class 10 trip, 690 V max, supplied with 3RT2015-1AK62 contactor and 3RA1921-1DA00 link module, snaps onto 60 mm busbar.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RA2210-1ED15-2AK6 — Identification
ParameterValue
Product designationnon-fused load feeders 3RA2
Main circuit poles3
BrandSIRIUS
Load feeder sizeS00
Product design / constructionreversing starter
Circuit-breaker sizeS00
Included contactor (type)3RT2015-1AK62
Included circuit-breaker (type)3RV2011-1EA10
Included link module (type)3RA1921-1DA00

Ratings & Performance

3RA2210-1ED15-2AK6 — Ratings & Performance
ParameterValue
Rated motor power at 400 V1 500 W
Operational current Ie, AC-3 at 400 V3.6 A
Rated voltage at AC-3, max.690 V
Rated motor power at 460/480 V (hp)2 hp
Rated motor power at 575/600 V (hp)3 hp
Rated current at 480 V3.95 A
Rated current at 600 V4 A
Rated operating frequency50 ... 60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Rated insulation voltage Ui (AC, pollution degree 3)690 V
Mechanical service life, typ. (switching cycles)30 000 000

Protection & Tripping

3RA2210-1ED15-2AK6 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Short-circuit protectionYes
Rated short-circuit current at 400 V (IEC 60947-4-1)153 000 A
Overload release setting range (current)2.8 ... 4 A
Overload release typethermal (bimetallic)
Short-circuit trip typemagnetic
Duty / utilization type (IEC 60947-6-2)2

Contacts & Control

3RA2210-1ED15-2AK6 — Contacts & Control
ParameterValue
Rated value690 V
Rated voltage range at 50 Hz110 V
Auxiliary switch extensionYes
Switching contact typeelectromechanical

Mechanical & Connection

3RA2210-1ED15-2AK6 — Mechanical & Connection
ParameterValue
Main circuit connection typescrew-type terminals
Main contact conductor range (AWG)2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
Mounting / fastening methodfor snapping onto 60 mm busbar systems
Mounting positionvertical
Width90 mm
Height200 mm
Depth155.1 mm

Environmental

3RA2210-1ED15-2AK6 — Environmental
ParameterValue
Operating temperature range-20 ... +60 °C
Storage temperature range-50 ... +80 °C
Transport temperature range-50 ... +80 °C
Pollution degree3
Shock resistance (IEC 60068-2-27)6g / 11 ms

Product details

Reversing starter in the SIRIUS S00 frame

The 3RA2210-1ED15-2AK6 is a Siemens SIRIUS non-fused reversing starter — a factory-assembled combination of a contactor, overload relay, and link module in one package, sized S00. It's built for reversing motor control in a single DIN-rail or busbar footprint.

Mounting and panel fit — busbar snap-on

This starter snaps onto 60 mm busbar systems — no DIN rail adapter needed if your panel uses that busbar pitch. The mounting position must be vertical; horizontal mounting isn't supported here. Dimensions are 200 mm high, 90 mm wide, and 155.1 mm deep. Clearance requirements: 20 mm upwards, 10 mm downwards, 9 mm at the sides, and zero forwards or backwards. That zero forward/backward clearance means you can butt it against the backplane or enclosure wall without derating.

Electrical ratings and duty

Rated insulation voltage is 690 V, with the AC-3 maximum operating voltage also at 690 V. Motor power ratings at common line voltages: 1 500 W at 400 V, 2 200 W at 500 V, and 3 000 W at 690 V. For 230 V single-phase applications, it's rated 0.75 hp. The degree of pollution is 3, so it's suited for industrial environments where conductive dust or occasional condensation is present — typical for motor control centers and panel shops.

Environmental and lifecycle

Operating temperature range is -20 to +60 °C, with storage and transport from -50 to +80 °C. That covers unheated warehouses and shipping through temperature extremes.

Frequently asked questions

What is the trip class and what does it mean for motor starting?

This is standard for general-purpose motors that accelerate to full speed within a few seconds — fans, pumps, and compressors with normal starting duty.

Does this reversing starter include the contactor and link module?

Yes, it ships with the 3RT2015-1AK62 contactor and the 3RA1921-1DA00 link module already factory-integrated. No separate ordering of those components is needed.

MPN